<4 Device Tag Extension Mode>

4-2

IM 01R01A20-01E

Synchronizing Devices with HART Device Tag Display Format

The same Device Tag Extension Mode needs to be set on PRM and FieldMate. Even if the user

renames the device tag on one side, it is updated to the other side after the synchronization as

long as the HART Device Tag Display Format of the device is consistent with the HART Device

Tag Display Format on the other side.

Sample case is shown as below, if HART Device Tag Display Format is set to “Tag+Descriptor”

and all the devices in the database are registered or updated with the same mode, then the

following outcomes can be expected.

Table 4-2

Sample case with same setting mode

PRM devices

Current mode:

Tag+Descriptor

Operation and Outcome

FieldMate devices Current mode:

Tag+Descriptor

EJX004-PIPE02

Registered mode:

Tag+Descriptor

Restore OK

[Not exist]

[Not exist]

Backup OK

EJA005-PIPE02

Registered mode:

Tag+Descriptor

EJA001-PIPE01

Registered mode:

Tag+Descriptor

Sync OK

EJA001-PIPE01

Registered mode:

Tag+Descriptor

Sync OK

Registering devices using PRM/FieldMate Synchronization means that the devices do not exist

in PRM database originally and the devices are imported from FieldMate.
In HART Device Tag Display Format is enabled, it can be expected that the device tags of the

devices imported to PRM do match the device tags shown in FieldMate.

However, if the HART Device Tag Display Format of the device in the database does not match

the mode of the other side, then the synchronization of the device is prohibited.

Table 4-3

Sample case with different device setting mode

PRM devices

Current mode:

Tag+Descriptor

Operation and Outcome

FieldMate devices

Current mode:

Tag+Descriptor

EJX006

Registered mode:

Tag

Prohibit Restore

[Not exist]

[Not exist]

Prohibit Backup

EJA007

Registered mode:

Tag

EJX002

Registered mode:

Tag

Prohibit Sync

EJX002-PIPE01

Registered mode:

Tag+Descriptor

Sync OK

EJA003-PIPE02

Registered mode:

Tag+Descriptor

Sync OK

EJA003

Registered mode:

Tag

Prohibit Sync