Synchronizing devices in stardom upstream project – Yokogawa FieldMate User Manual

Page 29

Advertising
background image

<4 Device Tag Extension Mode>

4-3

IM 01R01A20-01E

Synchronizing Devices in STARDOM Upstream Project

TIP

The followings describes sample case and operation work flow only for STARDOM user.

In STARDOM upstream project, the synchronization between PRM and FieldMate works except

the project name portion of the extended device tag. Project name is ignored.

Table 4-4

Sample case with project setting mode

PRM devices

Current mode:

Tag+Descriptor+Project Name

Operation and Outcome

FieldMate devices

Current mode:

Tag+Descriptor

[Not exist]

(Backup as “EJA005-PIPE02”)

Backup OK

EJA005-PIPE02

Registered mode:

Tag+Descriptor

EJX004-PIPE02_WELL01

Registered mode:

Tag+Descriptor+Project Name

Restore OK

[Not exist]

(Restored as “EJX004-PIPE02”)

EJA001-PIPE01_WELL01

Registered mode:

Tag+Descriptor+Project Name

Sync OK

EJA001-PIPE01

Registered mode:

Tag+Descriptor

Sync OK

In STARDOM upstream project, since the devices imported from FieldMate do not contain device

path information, it is also expected that the device tags of the imported devices do not contain

the project name, and the device tags can be updated with the project name only after Plug &

Play.

If the device has been synchronized before, renaming the device tag on one side will still update

the device tag on the other side properly after synchronization. The same behavior can be

expected for the other way around.

Table 4-5

Sample operation flow with project setting mode

Step Procedure

PRM

Current mode:

Tag+Descriptor+Project Name

Direction

FieldMate

Current mode:

Tag+Descriptor

Outcome

1

Before Sync

EJX004-PIPE02_WELL01

[Not exist]

2

Restore device

to FieldMate

EJX004-PIPE02_WELL01

EJX004-PIPE02

Device is restored

without the project

name portion

3

Rename the

device tag on

FieldMate

EJX004-PIPE02_WELL01

EJX004-PIPE02

EJX001-PIPE01

Device is renamed

on FieldMate

4

Synchronize

device back to

PRM

EJX004-PIPE02_WELL01

EJX001-PIPE01

5

After Sync

EJX001-PIPE01_WELL01

EJX001-PIPE01

Device is updated

in PRM while

keeping the project

name portion

8th Edition : May 31, 2013-00