1 configuration, Configuration -2 – Yokogawa FieldMate User Manual
Page 10

<2 OUTILINE>
2-2
IM 01R01A11-01EN
2.1
Configuration
The following equipment is required to use Verification Tool ver. 1.01.00;
• YOKOGAWA magnetic flowmeter AXF with HART Communication (AXF Output Signal and
Communication suffix code: -E).
• PC (*1) and Printer
• Magnetic Flowmeter Calibrator AM012 (Only for Enhanced VF (*2), Optional)
• Handy Calibrator CA150 or equivalent (Only for Enhanced VF (*2), Optional)
• Insulation Checker (Only for Enhanced VF (*2), Optional)
*1: Regarding the PC environment, refer to IM 01R01A01-01E Part B,C.
*2: VF stands for “Verification”.
F020301.ai
- Circuit Check
- Device Status Check
- Physical Appearance Check
USB FieldMate Modem
PC
Printer
Magnetic
Flowmeter
AXF
Insulation checker
(Optional)
Magnetic Flowmeter
AXF
- Insulation Resistance
Check
- Current Output Check
- Pulse Output Check
- Converter Check
CA150
Handy Calibrator
(Multi-meter)
(Optional)
MA012
Calibrator
(Optional)
Output Signal
4-20mA or pulse
Figure 2.1.1 Configurations