3 model and suffix codes, 4 options, Model and suffix codes -2 – Yokogawa PK200 User Manual

Page 11: Options -2

Advertising
background image

IM 21B03D01-01E

2-2

2. OVERVIEW

TIIS Intrinsically Safe (/JS3):

Intrinsically Safe Ex ia IIC T4
Certificate: TC18266

Explosionproof Construction:

TIIS Explosionproof (/JF3): Flameproof Exd II

B+H

2

T6X

FM Explosionproof (/FF1): Explosionproof for Class

I, Division 1, Groups B, C and D.
Dust ignitionproof for Class II/III,
Division 1, Groups E, F and G.
Temperature Class: T6.
Outdoor hazardous locations, NEMA
4X.

Dustproof Construction: IEC IP54
Connections:

Air Connection: Rc1/4 or 1/4NPT female
Electrical Connection: G1/2, G3/4 female or

1/2NPT, 3/4NPT female

Mounting:

Vertical or horizontal 50mm (2-
INCH) pipe mounting
Wall mounting

Mass (weight):

2.8kg (6.1lb)

Accuracy:

±0.5% of span

Linearity:

±0.2% of span

Hysteresis:

0.2% of span

Repeatability: 0.1% of span

2.3 Model and Suffix Codes

PK200

Input Signal -A

4 to 20mA DC

-C

4 to 20mA/10 to 50mA DC selection type

Output Signal

1

Output signal Pa calibration

20 to 100kPa

scale 0 to 200kPa

2

Output signal Pa calibration

40 to 200kPa

scale 0 to 400kPa

3

Output signal kgf/cm

2

calibration 0.2 to 1.0 kgf/cm

2

scale 0 to 2kgf/cm

2

4

Output signal kgf/cm

2

calibration 0.4 to 2.0 kgf/cm

2

scale 0 to 4kgf/cm

2

5

Output signal bar calibration

0.2 to 1.0bar

scale 0 to 2bar

6

Output signal bar calibration

0.4 to 2.0bar

scale 0 to 4bar

7

Output signal P calibration

3 to 15psi

scale 0 to 30Psi

8

Output signal P calibration

6 to 30psi

scale 0 to 60Psi

9

Output signal P calibration

6 to 27psi

scale 0 to 60Psi

Connections

1

Air connection: Rc 1/4, Electrical connection: G1/2 female

2

Air connection: Rc 1/4, Electrical connection: G3/4 female

3

Air connection: 1/4 NPT female, Electrical connection: 1/2NPT female

4

Air connection: 1/4 NPT female, Electrical connection: 3/4NPT female

Option

/

See section 2.4.

Model

Suffix Code

Description

T0202.EPS

2.4 Options

• Option Code/JF3: JIS Flameproof

TIIS flameproof Exd II B+H

2

T6X

• Option Code/G11: Packing adapter for TIIS Flame-

proof
Electrical connection: G1/2 female, Applicable cable
O.D.: 8 to 12mm

• Option Code/G21: Packing adapter for TIIS Flame-

proof
Electrical connection: G3/4 female, Applicable cable
O.D.: 10 to 16mm

• Option Code/FF1: FM Explosionproof

• Option Code/JS3: TIIS Intrinsically Safe

Applicable only with input signal code-A.

• Option Code/CS1: CSA Intrinsically Safe

• Option Code/SCF-

ᮀ: Special Color Finished on

converter cover
Allows the paint color of only a converter cover to
be selectable by specifying the color in the specifi-
cation item with reference to GS22D1F1.

• Option Code/X1: Epoxy Paint

Epoxy resin-baked coating.
Not applicable for special color finished.

Advertising