3 troubleshooting flow, Troubleshooting flow -2 – Yokogawa PK200 User Manual

Page 28

Advertising
background image

IM 21B03D01-01E

7-2

7. TROUBLESHOOTING

7.3 Troubleshooting Flow

The PK200 current-to-pneumatic converter causes
relatively few problems as long as it is used correctly.
However, inadequate preparation such as in mounting
or service conditions may result in a problem.

If the converter does not operate normally, take correct
measures by following the flow chart below. Some
problems include a complex cause which may not be
uncovered by the following flow chart. If a problem
appears difficult to correct, contact our service person-
nel.

Replace the converter using a spare.

F0702.EPS

Supply air at normal supply pressure.

Provide heat protection or good
ventilation.

Large output error.

NO

YES

YES

NO

Is air

supplied at normal supply

pressure?

Is the

converter installed

in a place subject to large

temperature changes?

NO

Is control relay defective?

Replace the control relay.

YES

Supply air at normal supply pressure.

Select “A.”

NO

YES

NO

YES

Is air

supplied at normal supply

pressure?

Is A / M selector switch

set to A?

NO

Is the restrictor clogged?

Clean the restrictor.

YES

Replace the converter using a spare.

F0703.EPS

NO

Is control relay defective?

Replace the control relay.

YES

The converter does not operate even when
input signal is applied.