IM 21B03D01-01E

4-4

4. WIRING AND PIPING

4.2.3 Grounding

(1) Provide grounding with a ground resistance of

100

Ω.

(2) Grounding terminals are provided inside and

outside of the terminal box. Use either terminal.

(3) Use 600V PVC insulated wire for grounding

wiring.

Figure 4.5 Intrinsically Safe Type Wiring

F0404.EPS

Current signal

Ground

G

ϩ

Ϫ

Figure 4.4 Wiring

4.3 Intrinsically Safe Type Wiring

The wiring of the intrinsically safe circuit between the
converter and the safety barrier must be kept routed
with sufficient physical separation from other circuits
so as not to be affected by electromagnetic induction,
etc., and should be implemented using metallic conduit
or shielded cable.