IM 21B03D01-01E

5-4

5. OPERATION

5.4 Range Adjustment

Perform the following to change to an output signal
other than those specified in Table 5.4 “Output
Signals.”

Zero point adjustable range is

±10% of span and the

span adjustable range is from 100 to 125%.

An output signal can be flexibly regulated within these
ranges using the zero and span adjustments.

Table 5.7 Zero and Span Adjustable Ranges

Output Signal Code Zero Adjustable Range Span Adjustable Range

1

12 to 28kPa

80 to 100kPa

2

*1

24 to 56kPa

160 to 200kPa

3

0.12 to 0.28kgf/cm

2

0.8 to 1.0kgf/cm

2

4

*2

0.24 to 0.56kgf/cm

2

1.6 to 2.0kgf/cm

2

5

0.12 to 0.28bar

0.8 to 1.0bar

6

*3

0.24 to 0.56bar

1.6 to 2.0bar

7

1.8 to 4.2psi

12 to 15psi

8

*4

3.6 to 8.4psi

24 to 30psi

9

*5

0.6 to 5.4psi

24 to 30psi

*1 Please set the supply air pressure at the maximum working

pressure plus 30 to 60kPa.

*2 Please set the supply air pressure at the maximum working

pressure plus 0.3 to 0.6kgf/cm

2

.

*3 Please set the supply air pressure at the maximum working

pressure plus 0.3 to 0.6bar.

*4 Please set the supply air pressure at the maximum working

pressure plus 4 to 7psi.

*5 Please set the supply air pressure at the maximum working

pressure plus 7 to 9psi.

T0507.EPS

5.5 4 to 20mA/10 to 50mA Selec-

tion

Take the following steps to select an input signal by
using 4 to 20mA/10 to 50mA selecting function.

4 to 20mA or 10 to 50mA can be selected by changing
the SOCKET switch on the amplifier shown in Figure
5.4. (Input signal is calibrated at 4 to 20mA at the time
of delivery.)

For 4 to 20mA input, insert the SOCKET switch to the
two right pins. For 10 to 50mA input, insert the
SOCKET switch to the two left pins.

NOTE

Before switching the SOCKET switch, always cut
off the input signal.

Figure 5.4 4 to 20mA/10 to 50mA Selection