3 storage precautions, 4 precautions for installation area, 5 installation of intrinsically safe type – Yokogawa PK200 User Manual

Page 7: 1 csa intrinsically safe type, Storage precautions -2, Precautions for installation area -2, Installation of intrinsically safe type -2, Csa intrinsically safe type -2

Advertising
background image

IM 21B03D01-01E

1-2

1. HANDLING PRECAUTIONS

1.3 Storage Precautions

(1) Select a storage place :
• Which is protected from rain and water.
• Which is free from vibration and impact.
• Whose temperature and humidity are as specified

below. Room temperature and humidity (approx.
25

°C and 65%) are more recommendable.

Temperature: -10 to 60

°C

Humidity: Less than 80%

(2) Store the converter in the packing condition of

shipment from YOKOGAWA whenever possible.

1.4 Precautions for Installation

Area

To use the converter stably for a long time, determine
an installation place, taking into account the following.

(1) Ambient Temperature
Avoid installing the instrument in a place subject to a
large temperature gradient and variations. If the
instrument is subject to plant-generated heat radiation,
take measures such as provision of heat protection and
good ventilation.

(2) Atmospheric Conditions
Avoid installing the converter in corrosive atmosphere.
Should it be used in corrosive atmosphere, make
provision for maintaining good ventilation.

(3) Magnetic Field
Please contact us in the case this instrument is installed
the strong Magnetic Field.

1.5 Installation of Intrinsically

Safe Type

1.5.1 CSA Intrinsically Safe Type

Hazardous Location

Non-hazardous Location

+

+

+

PK200
Current-to-
pneumatic Converter

[Intrinsically Safe]

F0105.EPS

Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G

Safety Barrier

General
Purpose
Equipment

+

Hazardous Location

Non-hazardous Location

+

+

PK200
Current-to-
pneumatic Converter

Class I, II, III, Division 2,
Groups A, B, C, D, E, F, G
Class III, Division 1.

General
Purpose
Equipment

[Nonincendive]

Note: Not use safety Barrier

Figure 1.4 Installation of CSA Intrinsically Safe Type

1. PK200 current to pneumatic converter is

applicable for use in hazardous locations:

• Intrinsically Safe for Class I, Division 1, Groups A,

B, C & D, Class II, Division 1, Groups E, F & G
and Class III, Division 1 Hazardous Locations.

• Nonincendive for Class I, Division 2, Groups A, B,

C & D, Class II, Division 2, Groups F & G, and
Class III, Division 1 Hazardous Locations.

• Outdoor Hazardous Locations, Encl Type 4X.
• Temperature Class: T4
• Ambient Temperature: -40 to 60

°C

2. Entity Parameters
• Intrinsically safe apparatus parameters

Vmax = 30V
Imax = 165mA
Pmax = 0.9W
Ci = 2nF
Li = 730

µ H

• Associated apparatus parameters (CSA Certified

Barriers)

Voc

≤ 30V

Isc

≤ 165mA

Pmax

≤ 0.9W

Advertising