4-14

IM 04L41B01-17E

Login Log

• The FL command is used to output the data.
• A log of users that have logged in and logged out is output. Up to 50 login/logout logs

are retained. Logs that exceed 50 are cleared from the oldest data.

• If the power goes down while logged in, you will be logged out. In this case, however,

it will not be recorded as a logout.

Syntax

EACRLF
yy/mo/dd_hh:mm:ss_xxxxxxxxxx_nnn_uuu···uCRLF
···································
ENCRLF

yy Year (00 to 99)
mo Month (01 to 12)
dd Day (01 to 31)
hh Hour (00 to 23)
mm Minute (00 to 59)
ss Second (00 to 59)

xxxxxxxxxx Login history is output left-justified.

Login:

Login

Logout:

Logout

NewTime:

New time

TimeChg:

Time change

PowerOff:

Power Off

PowerOn:

Power On

TRevStart:

Start of gradual time adjustment

TRevEnd:

End of gradual time adjustment

TimeDST:

Switching of the daylight savings time

SNTPtimset:

Time change by SNTP

CCSetEnd:

Completion of calibration correction

CCExpire:

Passing of the calibration due date

nnn Operation property

KEY:

Key operation

COM:

Communication

REM:

Remote

ACT:

Event action

SYS:

System

uuu···u User name (up to 20 characters)
_ Space

• Example

EA
99/05/11 12:20:00 Login KEY administrator
99/05/11 12:30:00 Logout KEY administrator
99/05/11 12:20:00 Login COM user
99/05/11 12:30:00 Logout COM user
EN