Appendix 1 Data Dropout during Modbus

Communication

Data Dropout during Modbus Client

If the response to the previous command is not complete when the DX attempts to issue
a command to a server device, the DX command cannot issue the command causing a
data dropout. Take appropriate measures by referring to the following figures.

Read cycle

Data dropout

(Servers 2 and 3)

Data dropout

(Server 3)

Server device 1

Server device 2

Server device 3

G

G

G

G

G

G

Read cycle

(Retry)

: Status lamp

: Response from the server device

: Command from the DX

Data dropout

(Servers 2 and 3)

Server device 1

Server device 2

Server device 3

Read cycle

Timeout value

Connection dropped

Data dropout

(Servers 2 and 3)

Server device 1

Server device 2

Server device 3

G

G

G

G

G

G

G

O

Connection dropped

Connection recovered

Timeout value

G

G

G

G

O

Y

Connection retry time*

G

G

G

G

G

G

Y

O R

1. When the response from the server device takes a long time

2. When the connection is dropped because there is no response from the server device

3. When the communication recovers by connection retry

* The first connection retry after the connection is

dropped is shorter than the specified interval. The

status lamp condition is an example when

connection retry is configured.