IM 04L41B01-17E

Using the Ethernet Interface

1

2

3

4

5

6

App

Index

1.13 Using the Maintenance/Test Server

When Not Using the Login Function

Access the server using the user name “admin” or “user.” You can use either the
administrator (admin) or user commands, depending on which name you used to log in.

When Using the Login Function (Standard)

Log in as an administrator or user who has been registered on the DX. Of the commands
in chapter 3, you can use either the administrator or user commands, depending on
which name you used to log in.

On DXs with the /AS1 Advanced Security Option

Access the server using the user name “admin” or “user.” You can use either the
administrator (admin) or user commands, depending on which name you used to log in.

Telnet Operation Example

The example below shows how to perform operations using Telnet on Windows XP.
The necessary operations vary depending on the operating environment. Perform the
operations that are appropriate for your environment.

Connecting

Type “telnet” in the Windows command prompt, and then press ENTER to start Telnet. If
you enter “display,” the Telnet settings are displayed. Configure the settings as indicated
below.
• Use local echo
set localecho
• Send CR and LF by pressing ENTER
set crlf
Connect to the DX using the “open” command.
open (the DX IP address or host name) 34261

* Put a space between the DX IP address or host name and “34261.”
“34261” is the port number of the maintenance/test server.

The DX returns the following message:
E1 402 “Select username from ‘admin’ or ‘user’.”

Access the server using the user name “admin” or “user.”

Sending Commands

For information about commands, see section 3.2.

Disconnection

The connection is closed when:
• A command is sent that closes the connection.
The quit command is sent.
• A communication timeout occurs.
The DX automatically closes the connection of clients with whom no communication

has taken place for 15 minutes.

• There is a communication error.
The connection is closed when there is a transfer error, a reception error, or when the

keepalive function times out (see “Other Functions” in section 1.1).