Wiring clamped terminals – Yokogawa Button Operated MV2000 User Manual

Page 25

Advertising
background image

Wiring Clamped Terminals

Remove the terminal block.

Hold both ends of the

terminal block and

pull straight.

Input signal wire

First, loosen the screw at the front using a

flat-blade screwdriver. Insert the input signal

wire into the slit on the left side of the terminal

block, and fasten the screw at the front.

Recommended wire size

0.08 to 1.5 mm

2

(AWG28 to 16)

Recommended length

of stripped wire:

7 mm

Connect the wires.

Flat-blade

screwdriver

Hold both ends of the terminal

block, align it with the connector,

and then push it in.

Connect the terminal block.

Note

RTD input terminals A and B are isolated on each channel. Terminal b is shorted internally
across all channels. However, terminal b is also isolated on each channel on models with the
/N1 option (Cu10, Cu25 RTD input/3-wire isolated RTD) and /N2 option (3-wire isolated RTD).

Connecting Input Cables

25

IM MV1000-02E

Advertising
This manual is related to the following products: