Meas channel > alarm mark, Meas channel > color scale band, Meas channel > calibration correction – Yokogawa Button Operated MV2000 User Manual

Page 41: Math channel > expression, alarm, Math channel > constant

Advertising
background image

Meas channel > Alarm mark

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (channel number) 1 to 24

1

Mark kind

Alarm/Fixed

Alarm

Indicate on Scale

On/Off

Off

Alarm mark color > Alarm 1

to 4

Red/Green/Blue/B.violet/Brown/Orange/Y.green/

Lightblue/Violet/Gray/Lime/Cyan/Darkblue/Yellow/

Lightgray/Purple/Black/Pink/L.brown/L.green/Darkgray/

Olieve/DarkCyan/S.green

Alarm 1: Red
Alarm 2: Orange
Alarm 3: Orange
Alarm 4: Red

Meas channel > Color scale band

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (channel number) 1 to 24

1

Band area

Off/In/Out

Off

Color

Same as the mark color

Lime

Display position > Lower

Numeric value (measurement range)

0.0000

Display position > Upper

Numeric value (measurement range)

0.0100

Meas channel > Calibration correction

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (channel number) 1 to 24

1

Number of set points

Off/2/3/4/5/6/7/8/9/10/11/12/13/14/15/16

Off

MES val

Value in the measuring range/measured value

–2.0000

True val

Numeric value (measurement range)

–2.0000

Math channel > Expression, Alarm

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (computation channel number) 101 to 124 101

Math

On/Off

Off

Calculation expression

Character string (up to 120 characters)

01

Span Lower

Numeric value (–9999999 to 99999999, Decimal place 0

to 4)

–200.00

Span Upper

Numeric value (–9999999 to 99999999, Decimal place 0

to 4)

200.00

Unit

Character string (up to 6 characters)

Alarm > 1 to 4

On/Off

Off

Type

H/L/T/t

H

Value

Numeric value

0.00

Relay

On/Off

Off

No.

I01 to I06/S01 to S30

I01

Detect

On/Off

On

Math channel > Constant

Setting

Selectable Range or Choices

Default Value

Number of constant

K01–K60

K01

Input

Numeric value (–9.9999E+29 to –1.0000E–30,

0,
1.0000E–30 to –9.9999E+29)

1

Math channel > Tag, Memory, Delay

Setting

Selectable Range or Choices

Default Value

First-CH, Last-CH

Numeric value (computation channel number) 101 to 124 101

Tag > Characters

Character string (up to 16 characters)

Memory sample > On/Off

On/Off

On

Alarm delay > Time

Numeric value (1 to 3600) s

10

Default MV1000 Settings

41

IM MV1000-02E

Advertising
This manual is related to the following products: