Strain input module, Pulse input module, Digital input module – Yokogawa Standalone MW100 User Manual

Page 6: Analog output module, Digital output module

Advertising
background image



IM MW100-0E

Universal Input Module, DCV/TC/DI Input Module, and Four-Wire RTD Resistance

Input Module

Model

Suffix Code

Description

MX110

Input type

-UNV

For DCV/TC/DI/3-wire RTD input

-VTD

For DCV/TC/DI input

-V4R

For DCV/DI/4-wire RTD/4-wire resistance input

Number of channels and

measurement interval

-H04

*1

4-CH, high-speed measurement (minimum measurement Interval: 10 ms)

-M06

*1

6-CH, medium-speed measurement (minimum measurement interval: 100 ms)

-M10

*1

10-CH, medium-speed measurement (minimum measurement interval: 100 ms)

-L30

*1

30-CH, medium-speed measurement (minimum measurement interval: 500 ms)

Options

/NC

*2

Without the plate with the clamp terminals

/H3

*3

M3 screw terminals

*1 “-H04” or “-M10” must be selected if “-UNV” is selected. “-M06” must be selected if “-V4R” is selected. “-VTD” must be

selected if “-L30” is selected.

*2 The “/NC” option can be specified only when “-M10” is specified.
*3 The “/H3” option can be specified only when “-L30” is specified.

Strain Input Module

Model

Suffix Code

Description

MX112

Input type

-B12

Internal bridge resistance: 120 Ω

-B35

Internal bridge resistance: 350 Ω

-NDI

NDIS connector for connections to an external bridge head

Number of channels and

measurement interval

-M04

4-CH, medium-speed measurement (minimum measurement and

measurement interval: 100 ms)

Pulse Input Module

Model

Suffix Code

Description

MX114

Input type

-PLS

Non-voltage contact, 5-V logic, open collector input

Number of channels and

measurement interval

-M10

10-CH, medium-speed measurement (minimum measurement interval: 100 ms)

Options

/NC

Without the plate with the clamp terminals

Digital Input Module

Model

Suffix Code

Description

MX115

Input type

-D05

Non-voltage contact, 5-V logic, open collector input

-D24

24 V logic input

Number of channels and

measurement interval

-H10

10-CH, high-speed measurement (minimum measurement and measurement

interval: 10 ms)

Options

/NC

Without the plate with the clamp terminals

Analog Output Module

Model

Suffix Code

Description

MX120

Output type

-VAO

Voltage/current output

-PWM

Pulse width modulation output

Number of channels and

output update interval

-M08

8-CH, minimum output update interval: 100 ms

Digital Output Module

Model

Suffix Code

Description

MX125

Output type

-MKC

A contact output

Number of channels and

output update interval

-M10

10-CH, minimum output update interval: 100 ms

Checking the Contents of the Package

Advertising