4.2

Commands/Responses at the PLC

The PLC sends commands and receives responses to commands. The commands
and responses that can be used are as follows.

4.2.1

Command/Response Component Elements

Commands sent from the PLC to the VJ Series signal conditioners are configured as
shown below.

Number of Bytes

1

1

2

2

1

1

1

1

Number of BCD Digits

2

2

1

4

4

2

2

1

1

1

Command/Response

Element

Address

number

(ADDRESS)

Parameter

number

CPU

number

01

CR

(0D)

LF

(0A)

5th

digit

0

+/-

0

Data

040201E.EPS

Variable only for responses.
A maximum of 64 data items

(1)

Address number (01 to 99)

Numbers used by the PLC to identify the VJ Series signal conditioners at the commu-
nication destination. (They are identification number specific to individual VJ Series
signal conditioners.)

(2)

CPU number

This number is fixed to “01”.

(3)

Parameter number

This is 4-digit BCD data of a D register number, not including "D." No I-relays can be
specified.

See Also

Chapter 6 for more information on D registers.

(4)

0

This is fixed to "0."

(5)

0

This is fixed to "0" for commands, while it is 5th digit of read data for responses.

(6)

0

This is fixed to "0."

(7)

+/-

This is fixed to "0" for commands, while it is 0: positive data (+) or 1: negative data (-)
for responses.

(8)

Data

This is data to be read for commands, while it is the number of read data for re-
sponses.

(9)

CR and LF

These are the control codes indicating the end of a command. The corresponding
control character strings are CR, which is 0D in hexadecimal in ASCII code, and LF,
which is 0A in hexadecimal in ASCII code.