2 response error code[response, Message format in the event of error, Response error codes – Yokogawa JUXTA VJ Series Limit Alarms User Manual

Page 48

Advertising
background image

5-8

<Toc> <Ind>

<5. MODBUS Communication >

IM 77J01J11-01E

3rd Edition : Oct. 15, 2007-00

5.2.2

Response Error Code[Response]

Message Format in the Event of Error

If there are any inconsistencies other than communication errors in a message, a VJ Series
signal conditioner does nothing, but returns the following message.

Number of bytes in RTU mode

Number of bytes in ASCII mode

2

2

Address

Number

(ADDRESS)

Element

Function Code

(*1)

Error Code

Error Check

[CR] [LF]

2

None

2

1

2

1

2

1

050220E.EPS

*1: The function code contains a function code (hexadecimal number) + number 80 (hexadecimal number).

Response Error Codes

Table 5-3 List of Error Codes

01

Error Code

Meaning

Description

02

D-register number error

Function code error

03

D-register count error

D-register number out of the range has
been specified.

No function code exists.

Number of D registers has been specified,
being out of the range.

050221E.EPS

Even when a message is sent, no response returns if:

Retransmission error (overrun, framing, parity, LRC, or CRC-16 error) was detected.

Address in an instructed message is incorrect.

Interval between data composing a message was 2 seconds or more.

CRC-16 or LRC values are incorrect.

Note: As a countermeasure, provide a timeout process in the communication functions of a higher-level device or in the

communication program.