Setup, 1 setup procedure, Connection – Yokogawa JUXTA VJ Series Limit Alarms User Manual

Page 9

Advertising
background image

<Toc> <Ind>

<1. Setup >

1-1

IM 77J01J11-01E

1.

Setup

This chapter describes the setup procedure required to use the communication
functions (PC link, Ladder, and MODBUS) and the communication parameters of the
VJ Series.

1.1

Setup Procedure

Set up the communication functions on the VJ Series as follows:

Set up the communication function parameters of the VJ Series. (See section 1.2.)

Connect a higher-level device and a VJ Series. (See the connection diagram below.)

Create communication programs for the higher-level device to perform communication.

010101E.EPS

Note: Refer to the documentation of each higher-level device when creating communication programs.

B (+)

A (-)

Shielded

B (+)

A (-)

B (+)

A (-)

VJ Series

VJ Series

PLC

Grounding resistance of less than 100

Grounding resistance of less than 100

Terminating resistor

220

1/4 W

Terminating resistor

220

1/4 W

• Connection

2

5

6

2

5

6

SG

COM

COM

B (+)

A (-)

B (+)

A (-)

B (+)

A (-)

VJ Series

VJ Series

PC or PLC

Grounding resistance
of less than 100

Terminating resistor

220

1/4 W

Grounding resistance
of less than 100

010102E.EPS

2

5

6

2

5

6

COM

COM

ML2

(RS-232C/RS-485 converter)

RS-232C

(straight cable)

4

3

5

SG

3rd Edition : Oct. 15, 2007-00