<4. Ladder Communication >

4-3

IM 77J01J11-01E

4.2.2

Reading Parameters

Parameters from the PLC are read in the VJ Series signal conditioners in the following
configuration. (The maximum number of data items to be read is 64.)

040204E.EPS

Data of parameter no. (n)

Data of parameter no. (a)

Data of parameter no. (b)

Number of Bytes

1

1

2

2

1

1

1

1

Number of BCD Digits

2

2

1

4

4

2

2

1

1

1

Command Element

Address

number

(ADDRESS)

Parameter

number

CPU

number

01

CR

(0D)

LF

(0A)

0

0

0

0

Number of

read data

(n)

2

1

1

1

1

1

4

2

2

1

1

1

CR

(0D)

LF

(0A)

5th

digit

0

+/-

0

ddddn

Number of Bytes

1

1

2

Number of BCD Digits

2

2

4

Response Element

Address

number

(ADDRESS)

Parameter

number

CPU

number

01

2

1

1

1

4

1

1

1

5th

digit

0

+/-

0

dddd1

2

1

1

1

4

1

1

1

5th

digit

0

+/-

0

dddd2

• • •

• • •

Example of reading the output value (D register 0008) of the VJ Series
signal conditioner with communication address-1

[Command]

01010008000000010D0A

The output value 500 (BCD code) is returned as a response to the above command (50.0%
is expressed as 500).

[Response]

010100080000005000D0A