<5. MODBUS Communication >

IM 77J01J11-01E

3rd Edition : Oct. 15, 2007-00

5.1.1

Configuration of Message

Messages sent from the higher-level device to the VJ Series consist of the following ele-
ments.

Number of bytes in RTU mode

None

Number of bytes in ASCII mode

2

2

(1)

(3)

(4)

(5)

(2)

(6)

Element

Address

Number

(ADDRESS)

Function Code

Start of

Message Mark

Data

Error Check

End of

Message Mark

None

1

2

2

4n

1

1

2n

2

050103E.EPS

(1)

Start of Message Mark

This mark indicates the start of a message. Note that only ASCII mode requires a
colon (:).

(2)

Address Number (1 to 99)

Address numbers are used by the higher-level device to identify the VJ Series signal
conditioners at the communication destination. (These numbers are identification
numbers specific to individual VJ Series, which are expressed in a hexadecimal in the
message.)

(3)

Function Code (See subsection 5.2.1, “List of Function Codes”)

This element specifies a command (function code) from the higher-level device.

(4)

Data

This element specifies D register numbers, the number of D registers, parameter
values, or others in accordance with the function code. (It is expressed in a hexadeci-
mal in the message.)

(5)

Error Check

In RTU mode

Carried out by the cyclic redundancy check (CRC-16) system.

In ASCII mode

Carried out by the longitudinal redundancy check (LRC) system.

(6)

End of Message Mark

This mark indicates the end of a message. Note that only ASCII mode requires CR +
LF.