Yokogawa JUXTA VJ Series Limit Alarms User Manual

Page 54

Advertising
background image

6-4

<Toc> <Ind>

<6. Functions and Usage of D Registers >

IM 77J01J11-01E

3rd Edition : Oct. 15, 2007-00

D0002, D0003: INPUT1_L, INPUT1_H (input value: engineering unit)

D0002 shows a numeric value and D0003 shows the number of digits below the decimal
point.

mA, mV, V

Number of digits

belowdecimal point

Input Units

Њ

C, K

2

1

060301E.EPS

D0004: input value (ratio of input value to input span is indicated as a

percentage)

D0008: output value (percentage indication)

Example 1:

When the input value (engineering unit) is 680.0

°

C for VJU7 (universal

temperature converter), thermocouple input, and type K (input range: 0 to
1000

°

C):

D0002: input value (engineering unit)

Contents of D registers

Internal value

D0004: input value (%)

02A8 (=680)

1A90 (=6800)

D0008: output value (%)

02A8 (=680)

68.0 (%)

68.0 (%)

D0003: input value (engineering unit),
number of digits below decimal point

0001 (=1)

680.0 (

Њ

C)

060302E.EPS

Example 2:

Representation of negative values

When the input value (engineering unit) is -10.5

°

C in the same conditions

as above:

D0002: input value (engineering unit)

Contents of D registers

Internal value

D0004: input value (%)

FFF5 (= -11)

FF97 (= -105)

D0008: output value (%)

FFF5 (= -11)

-1.1 (%)

-1.1 (%)

D0003: input value (engineering unit),
number of digits below decimal point

0001 (=1)

-10.5 (

Њ

C)

060303E.EPS

D0014, D0015: Alarms 1 and 2 ("1" when on or "0" when off)

D0041 to D0064: Revision, revision of menu table, tag number 1,

tag number 2, comment 1, and comment 2

One D register indicates two letters in the ASCII code.

For example, if D0049 to D0052 contain a tag called "YOKOGAWA," each D register
shows two letters as follows:

5 9 4 F

D0049

060304E.EPS

Y

O

4 B 4 F

D0050

K

O

4 7 4 1

D0051

G

A

5 7 4 1

D0052

W

A