Sterling TC User Manual

Page 26

Advertising
background image

26

Table 9 - Tubular Blower Troubleshooting Guide (continued)

SYMPTOMS

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

H. Condensation.

1. Improper venting.

2. Unit under fi red.

3. Building/space too cold.

1. Refer to "Installation."

2. Check gas supply pressures to unit. Refer to

"Installation."

3. Refer to "Installation."

I. Burners will not shut off.

1. Thermostat located improperly.

2. Improper thermostat wiring.

3. Shorted circuit.

4. Defective thermostat.

5. Defective/sticking gas valve.

6. Defective control board.

7. Excessive gas supply pressure.

1. Relocate thermostat away from outside wall

or drafts.

2. Check thermostat circuit for open and close

on heater terminal strip "R" and "W."

3. Check thermostat circuit for shorts or any

staples piercing wires.

4. If thermostat is calling after set point has

been satisfi ed, replace.

5. Check for 24V on gas valve terminals when

thermostat not calling. Replace if necessary.

6. Check for 24V at terminals "R" and "W." If not

present and board is not in fl ash code mode,
replace board.

7. Refer to "Pipe Installation" and Table 4 - "Gas

Piping Requirements."

J. Rapid burner cycling.

1. Loose electrical connections at thermostat or

gas valve.

2. Excessive thermostat heat anticipator setting.

3. Unit cycling on high limit.

4. Thermostat located improperly.

1. Tighten all electrical connections.

2. Adjust heat anticipator setting for longer

cycles. Refer to "Electrical Connections."

3. Check for proper air supply across heat

exchanger and proper gas supply.

4. Relocate thermostat away from outside wall

or drafts.

K. Blower will not run.

1. Loose electrical connections.

2. Defective motor or overload.

3. Defective control board.

4. Contactor or starter overload tripped.

5. Broken belt.

1. Check and tighten wires on blower circuit.

2. Test for 115V on terminal ACB Heat and "L2."

If voltage is present, replace motor.

3. Test for 115V on terminal ACB Heat and "L2."

If voltage is not present 45 seconds after trial
for ignition, replace board.

4. Test for 115V on coil of contactor. Check if

overload has tripped; reset. Check amp draw
to motor. Check incoming for power and
contactor operation.

5. Replace belt.

L. Blower motor turns on and off while

burner is operating.

1. Motor overload protection is tripping.

2. Loose wiring or connection.

3. Control board is defective.

1. Check motor amp against the motor name

plate, check voltage, replace if found
defective.

2. Check for 115V between motor leads.

3. Check terminal ACB Heat for voltage. If

voltage not constant, replace board.

M. Blower motor will not stop.

1. Control board is in fl ame failure mode.

2. Improperly wired blower circuit.

3. Control board is defective.

1. Turn 115V power off to the unit, wait 10

seconds and reapply voltage to the unit.

2. Check wiring of blower circuit to wiring

diagram.

3. If unit is not calling for heat and board is not

in fl ash code mode, replace board.

Advertising