Davey SS30-25 CIRCULATION PUMP User Manual

Page 2

Advertising
background image

1. GENERAL

1.1 Applications

SC20-25

For faster circulation of water in closed -

circuit domestic (individual) central heating

and air-conditioning systems.

SB25-20, SB30-25, SS30-25

For faster circulation of hot water in:

- Secondary hot water distribution loops.

- Industrial water loops (air conditioning,

cooling, tank circulating).

1.2 Specifications

• Temperature range:

-10

o

to +110

o

C

• Ambient temperature: up to +40

o

C

• Max. service pressure: 10 bar

• Min. suction pressure: 1.5m (0.15 bar)

(m w.g.*)

at +82

o

C;

3m (0.3 bar)

at +95

o

C;

10m (1 bar) at

+100

o

C

• Antifreeze

(water + glycol):

up to 50%

(with the exclusion of all other liquids

without first obtaining the written

approval from Davey Products Pty Ltd)

• Hardness of water (TH): max. 350ppm

• Recommended

flow velocity:

between 0.5

and 1m/s max

NOTE: This pump is not approved nor

intended for use in swimming

pools, spa pools or spa baths.

2. SAFETY

Read this data sheet carefully before

installing and starting up. Pay special

attention to the points concerning the

safety of the equipment for the end user.

2.1 Symbols used in the manual

Warning

Instructions concerning electricity

Calls attention to a potential

risk that might affect safety.

3.

TRANSPORT AND STORAGE

When taking delivery of the equipment,

check that it has not been damaged in

transit.

If the equipment delivered is to be

installed at a later time, store it in a

dry place and protect it from impact

and outside influences (moisture,

frost, etc).

4.

PRODUCTS AND ACCESSORIES

4.1 The Pump

With threaded ports according to model.

The motor has a wet rotor and the

bearings are self lubricating.

Three-speed with manual selection by

selector switch.

• Compliance:

TF10

• Insulation class:

F (155

o

C)

• Protection:

IP42

(only with terminal box at 6, clock

position on SS30-25).

4.2 Accessories

Supplied:

Unions with gaskets

Recommended: Non return valves

Isolating valves

5. INSTALLATION

5.1 Assembly (see FIG. 1&2)

- Make sure that the circulator is

accessible.

- Assemble directly on a pipe, preferably

vertical, and if possible on the boiler

return circuit; never at the low point (to

protect against deposits).

- The motor shaft axis must always be

horizontal.

- The arrow on the pump casing indicates

the direction of water flow (see FIG. 3).

- Install isolating valves on both sides of

the circulator to facilitate removal for

servicing.

If the circulator must

be insulated, we advise

against obstructing the

evacuation notches in the

motor flange (see FIG. 3).

~ 2 ~

~ 7 ~

Advertising