Davey SS30-25 CIRCULATION PUMP User Manual

Page 4

Advertising
background image

8.1 The circulator is noisy

a)

Air in circulator

- Bleed the circulator, loosen the rear

plug; continue until there are no more air

bubbles, then screw the plug back in.

b)

The suction pressure is too low

- Raise the pressure in the circuit.

c)

Considerable flowing water noise

- Consider a slower speed.

d)

Foreign bodies in impeller

- Remove the motor and clean the

impeller.

8.2 The circulator fails to start

a)

Shaft stalled by fouling after a

prolonged shutdown

- Free the shaft; remove the rear plug.

Use a flat bladed screwdriver to turn the

motor shaft. Then reinsert the rear plug

(see FIG. 7).

b)

No power supply to circulator

- Check that the motor is connected.

- Check the fuses of the installation.

c)

Capacitor defective

- Replace it; the characteristics are

indicated on the rear data plate ( FV).

For changing the capacitor lift-up the

fixing clip of the capacitors wires (see

FIG. 5 - rep. A). For removing the wires,

insert the new capacitor wires then

press the clip for locking.

d)

Foreign bodies in impeller

- Remove the motor and clean the

impeller.