Diagnostics – Hired-Hand Universal Ray Tube Heaters: AG2 Series Rev.11-07 User Manual

Page 13

Advertising
background image

13

3.0

Operation • Diagnostics

Chart 3.1 •

LED Fault Code Status

LED Code

Fault Status

Fault Code Delay*

Initial flash on power up,

No fault, normal operation

No Delay

then steady off


Steady ON

Module failure / Internal fault

No Delay


1 flash

Ignition failure

30 – 32 minutes


2 or 3 flashes

APS (Air Proving Switch)

10 – 12 minutes

(Fan / Intake / Exhaust)


4 flashes

Solenoid valve fault

No Delay

Leaky valve

Flame amplifier fault


No flash on 117V startup

Transformer fault

No Delay

*Some LED codes have a time delay before the LED will flash.

AG2

Series

Diagnostics

Lockout:

The controls will automatically lockout the heater system when an external or system fault occurs. There
are two types of lockout:

Soft Lockout: The heater will attempt to light three times. In the event of a failed attempt to light, (gas

pressure, valve, no flame sense etc.), the heater will enter a soft lockout period for 30
minutes and then attempt to light three more times before entering Hard Lockout mode.

Hard Lockout: If proof of flame is not established, a component failure occurs or blockages are evident,

the heater will enter hard lockout. If lockout occurs, the control can be reset by briefly
interrupting the power source. Refer to Chart 3.1 below for a description of LED codes.

Figure 3.1

LED Operation Indicator Lights

Note: Hard lockout LED CODE will appear upon completion of the soft lockout sequence of operation.

Light 1(amber)

Indicates High

Fire Mode

Light 2 (amber)

Indicates Low

Fire Mode

Light 3 (red)

Indicates Diagnostic

Fault Code Status

(see Chart 3.1)

Operational Indicator Lights