0 troubleshooting guide – Hired-Hand Universal Ray Tube Heaters: AG2 Series Rev.11-07 User Manual

Page 14

Advertising
background image

Check the power across the green

and white wires of the yellow control

cord. Is there 24V power?

Is the power across the 24V terminal and

the ground on the circuit board 24V?

Does the fan

blower turn on?

Is the power across the TH terminal

and ground on the circuit board 24V?

Is there 120V on the

primary side of the

internal transformer?

Is the power at

the heater 120V?

Find the source

of the electrical

problem between

panel and heater.

Does the ignitor

warm up and

glow red?

14

4.0

Troubleshooting Guide

4.0

Troubleshooting Guide

Turn up thermostat

No

Yes

Continued on page 16.

AG2

Series

Yes

No

No

Yes

No

The circuit board

is faulty and must

be replaced.

No

The internal

transformer is

faulty and must

be replaced.

Yes

Yes

No

The relay board is faulty

and must be replaced.

Yes

Is the LED flashing a fault code?

(See page 13 for code status, then

continue troubleshooting below.)

Is the circuit board

sending 120V to the fan?

No

Yes

Is the blower obstructed?

The blower

is faulty and must

be replaced.

No

Yes

Remove obstruction.

Yes