Hired-Hand Universal Ray Tube Heaters: AG2 Series Rev.11-07 User Manual

Page 16

Advertising
background image

Does the burner lite and then

immediately go out?

16

4.0

Troubleshooting Guide

Continued from page 14.

AG2

Series

After the ignitor is warmed up,

does the gas valve open?

Does the burner light?

Yes

Test for 24V at gas valve

during opening period (30-45

seconds after power to the

heater). Is there 24V to the

gas valve for 8 seconds?

No

No

The circuit board

and/or wiring

harness is faulty

and should be

replaced.

Confirm that gas pressure is within maximum and minimum inputs

as indicated on the heater’s rating plate. Is gas pressure OK?

Yes

Correct

problem.

Replace gas

valve.

Is the ball valve in

the ON position?

No

Yes

Confirm that gas pressure is within

maximum and minimum inputs as

indicated on the heater’s rating

plate. Is gas pressure OK?

Yes

Correct

problem.

Purge air from

gas lines.

Yes

Does the burner stay lit?

No

Yes

Does the burner

stay lit for at least

8 seconds and

then shut off?

Yes

Is the heater properly grounded?

Is the heater’s polarity correct?

Correct

problem.

Yes

Yes

No

No

No

No

Yes

Troubleshooting

ends.

Does the burner stay lit until

the call for heat ends?

Yes

The following can cause the heater to shut down:

• Improper grounding.

• High winds.

• Taking combustion air from attic space.

• Dirty environment.

• Improperly positioned baffle.

• Fluctuation gas pressure.

No