NOTICE

Bypassing any switch is intended for testing purposes only. Do not leave switch bypassed
during normal operation or the heater’s built-in safety mechanisms will be compromised.

Is there 120V on the primary side

of the external transformer?

Is there 24V on the secondary side

of the external transformer?

Is there 24V to the

thermostat?

15

4.0

Troubleshooting Guide

Key

Start

Question

Process

Question

Corrective

Action

AG2

Series

No

Find the source of the electrical

problem between panel and the

external transformer.

No

The transformer is faulty

and must be replaced.

Yes

No

Find source of electrical

problem between

the transformer and

thermostat.

Yes

The thermostat wiring

is faulty and should be

replace or repaired.

Yes