Ventilation, Ups cabinets, Ssc cabinets – APC GALAXY 7000 User Manual
Page 18: Installation
Advertising

Layout >
34020846EN/AD
- Page 18
1. Installation
Ventilation
UPS cabinets
SSC cabinets
Pn = rated power, for other values please consult the after-sales support or the local office.
The optimum operating-temperature range is
20 to 25°C.
An operating temperature of 35°C is possible,
but battery life will be reduced.
Size the ventilation system taking into
account the values in the table below.
Power rating in kVA
250
300
400
500
Air flow (m³/h)
6000
6000
6000
8300
Heat losses to be
evacuated at Pn
kW
14.3
17.2
22.9
27.2
Cal./s
3418
4111
5473
6501
Power rating in kVA
800
1200
2000
Air flow (m³/h)
1000
Natural
Natural
Heat losses to be
evacuated at Pn
kW
3.7
< 1
< 1.5
Cal./s
884
< 240
< 360