Characteristics of the connection terminals, Ups cabinets, Sscs, ssc maintenance, external bypass cabinets – APC GALAXY 7000 User Manual

Page 21: Power cables for single upss, Installation

Advertising
background image

Prerequisites >

34020846EN/AD

- Page 21

1. Installation

Characteristics of the connection terminals

UPS cabinets

SSCs, SSC maintenance, External bypass cabinets

Power cables for single UPSs

Connections are made to terminals that are pre-drilled or equipped with studs.
Earthing cables connect to the earthing bar.

Cabinets in kVA

Phase terminal

Earthing terminal

Battery terminal

Type of stud

Hole diameter in mm

Hole diameter in mm

Hole diameter in mm

250 M10

/

13

13

300 M10

/

13

13

400 M10

/

13

13

500 /

13

13

13

Cabinets in kVA

Phase terminal

Earthing terminal

Hole diameter in mm

Hole diameter in mm

800

13

13

1200

13

13

2000

13 and 17

13

AC cable sizes are determined for:

the TNS system for copper, single-core cables, type U1000 R02V, 100 m long with a line voltage drop <3%, installed on

perforated cable trays, XLPE-type insulation, single-layer trefoil formation, THDI between 15% and 33%, 35°C, at 400 V,
grouped in four touching cables.

Battery cable sized are determined for:
copper, single-core cables, type U1000 R02V, maximum length 25 m with a line voltage drop <1%.

UPS

cabinets in

kVA

Minimum size in mm²

Normal AC

line

Bypass AC

line

Load

Battery

250

1x150

1x150

1x150

1x150

300

1x240

1x240

1x240

1x185

400

2x150

2x150

2x150

1x240

500

2x240

2x240

2x240

2x150

Normal AC

Bypass AC

Load

UPS

General case

Normal AC

Load

UPS

Frequency converter