Characteristics of the connection terminals, Ups cabinets, Sscs, ssc maintenance, external bypass cabinets – APC GALAXY 7000 User Manual
Page 21: Power cables for single upss, Installation

Prerequisites >
34020846EN/AD
- Page 21
1. Installation
Characteristics of the connection terminals
UPS cabinets
SSCs, SSC maintenance, External bypass cabinets
Power cables for single UPSs
Connections are made to terminals that are pre-drilled or equipped with studs.
Earthing cables connect to the earthing bar.
Cabinets in kVA
Phase terminal
Earthing terminal
Battery terminal
Type of stud
Hole diameter in mm
Hole diameter in mm
Hole diameter in mm
250 M10
/
13
13
300 M10
/
13
13
400 M10
/
13
13
500 /
13
13
13
Cabinets in kVA
Phase terminal
Earthing terminal
Hole diameter in mm
Hole diameter in mm
800
13
13
1200
13
13
2000
13 and 17
13
AC cable sizes are determined for:
the TNS system for copper, single-core cables, type U1000 R02V, 100 m long with a line voltage drop <3%, installed on
perforated cable trays, XLPE-type insulation, single-layer trefoil formation, THDI between 15% and 33%, 35°C, at 400 V,
grouped in four touching cables.
Battery cable sized are determined for:
copper, single-core cables, type U1000 R02V, maximum length 25 m with a line voltage drop <1%.
UPS
cabinets in
kVA
Minimum size in mm²
Normal AC
line
Bypass AC
line
Load
Battery
250
1x150
1x150
1x150
1x150
300
1x240
1x240
1x240
1x185
400
2x150
2x150
2x150
1x240
500
2x240
2x240
2x240
2x150
Normal AC
Bypass AC
Load
UPS
General case
Normal AC
Load
UPS
Frequency converter