2.3 Electrical characteristics
Selection of protection devices
UPS short-circuit current with inverter coupled and bypass AC source out of tolerances
When sizing the upstream circuit breakers, the parameters presented below must be taken into account.
Time/current curves for UPS input and output fuses
Sn
250 kVA
300 kVA
400 kVA
500 kVA
In (at 400 V)
361 A
433 A
577 A
721 A
Isc
1085 A
1085 A
1446 A
1975 A
Q1
Q4S
Q5N
NORMAL AC
BYPASS AC
Upstream
CB
(not supplied)
Downstream
CB
(not supplied)
output
fuses
input
fuses
Upstream
CB
(not supplied)
Load
10
4
10
3
10
2
10
1
10
-
1
10
-
2
10
-
3
10
-
4
10
4
10
3
10
2
10
I (A)
t (s)
400 kVA : 800A
500 kVA : 1000A
250-300 kVA : 630A