Connecting the ups units in parallel, Connecting the modular ups units in parallel, Installation – APC GALAXY 7000 User Manual
Page 47

Connecting the control-wire cables >
34020846EN/AD
- Page 47
1. Installation
Connecting the UPS units in parallel
Connecting the modular UPS units in parallel
This operation must be carried out by qualified personnel.
The door must be open.
The supplied cables are 10 or 20 m long; The maximum total length must not exceed 180m.
On exiting the cabinet, the cables must run along the earthing and connection cables between cabinets.
Key
(1) Connectors
(2) Cable ties
(3) Exchange-current and CAN cables
Exchange current
1. Connect the XM2 and XM3
connectors in the two UPS units.
CAN
2. Fit a blue plug on connector XM6 in
UPS1.
3. Connect XM7 in UPS1 to
XM6 in UPS2.
4. Fit a red plug on connector XM7 in
UPS2.