Page 42: Connect the cables, Installation

Advertising
background image

Connecting the power cables >

34020846EN/AD

- Page 42

1. Installation

SSC maintenance cabinet

800 and 1200 kVA

R e m o v e t h e p r o t e c t i v e c o v e r s

This operation may only be carried out by authorized staff.

The door must be opened using the Ronis 405 key.

l

Key:

(1) Front face protective covers

(2) Roof protective cover

(3) Earth bar
(4) To Earth

(5) To the load

(6) To the SSC
(7) To the UPS

1 - Remove protective covers (1) and/
or (2).

C o n n e c t t h e c a b l e s

This operation may only be carried out by authorized staff.

See “Characteristics of the connection terminals”, page 21.

1 -Check switches Q3B ext (1) and

Q5N ext (2) are in the OFF position as
shown opposite.

2 - Connect the protective conductor
(PE or PEN) to the earth bar

3 - Connect the UPS conductors in the
following order: L1, L2, L3

4 - Connect the AC Bypass
conductors in the following order: L1,

L2, L3

5 - Connect the load conductors in the

following order: L1, L2, L3

6 - Refit the protective covers