2.0 INSTALLATION

2.1 LOCATION

The ability of a dehydrator to dry natural gas is dependent on

the correct location of the unit. Temperature and pressure are

the keys to selecting the proper location.

INLET GAS TEMPERATURE: Lower inlet gas temperatures will

result in a lower moisture content at the outlet of the dehydrator.

Locate the dehydrator at the point where temperature is the lowest.

CAPACITY: The chart below indicates the maximum flow rate

through the dehydrator for a 24 HOUR period. To calculate the

capacity for a rate per minute just multiply the

MSCFD RATE (from

chart ) by 0.6944 example:

A PLD 12-2.8 operating at 50 PSIG has a maximum MSCFD rate of

79. To figure the SCFM multiply 79 MSCFD x 0.6944 which equals

54.86SCFM

NOTE: This is the MAX instantanious flow that can be processed

through the dehydrator without deterioration of the drying
performance.

OPERATING PRESSURE: More gas can be processed through the

dehydrator at higher pressures. Locate the dehydrator at the highest

practical pressure, but do not exceed the maximum rated working

pressure of the dehydrator. Refer to the capacity chart located below.

AFTERCOOLING: If the gas being processed has been compressed

mechanically, an aftercooler, finned tubing or extended run of piping

will usually be necessary to reduce the inlet gas temperature to the

dehydrator.

MAXIMUM CAPACITIES - MSCFD

1,000 STANDARD CUBIC FEET PER DAY

250 PSIG

173

325

510

786

1147

1831

2749

225 PSIG

157

294

462

712

1038

1658

2490

200 PSIG

141

263

413

638

930

1485

2230

175 PSIG

124

233

365

563

822

1312

1970

150 PSIG

108

202

317

489

714

1139

1711

100 PSIG

75

141

221

341

497

793

1191

50 PSIG

42

79

125

192

280

447

672

MAXIMUM

WORKING

PRESSURE

280 PSIG

280 PSIG

280 PSIG

280 PSIG

280 PSIG

280 PSIG

280 PSIG

PART

NO.

80-1397

80-1399

80-1401

80-1403

80-1405

80-1468

80-1407

ALWAYS PROCESS THE GAS THROUGH THE

DEHYDRATOR AT THE LOWEST TEMPERATURE

AND THE HIGHEST PRESSURE.

IMPORTANT

280 PSIG

193

362

567

875

1277

2038

3061

1.0 OPERATION

A Pipeline Dehydrator removes the water vapor (humidity) pres-

ent in the gas stream. The process cleans and dries the gas as it

flows through a vessel which is filled with a special drying agent

(desiccant). The dehydrator operates automatically. There are no

moving parts and no external source of power is required.

"Wet" natural gas enters the lower portion of the dryer where liquid

water and solid particles are separated by gravity and fall to the

bottom of the vessel. The gas moves upward through the prebed

and drying bed of Van Gas desiccant tablets. The tablets attract

and absorb moisture from the gas as it flows through the desiccant

bed. The tablets dissolve gradually as they absorb the moisture

and the liquid falls to the bottom of the vessel. The liquid run off in

the prebed creates an extended surface area capable of removing

additional moisture from the gas. This conserves the absorbent

desiccant tablets. The "dry" natural gas flows through the dryer

outlet.

The solution of dissolved desiccant and water that falls into the

claim area at the bottom of the vessel must be drained regularly to

prevent the vessel from flooding. An automatic drain valve can be

installed to prevent the vessel from flooding.

CAUTION

The gas temperature should not exceed:

100°F for GASDRY PRIME

80°F for GASDRY PEAK

100°F for GASDRY MAX