P h 1, P h 2, Warning – HT instruments HT9022 User Manual

Page 22

Advertising
background image

HT9022

EN - 20

WARNING

If the frequency of the measured voltage is lower than 40Hz or higher than
70Hz, the display shows the message “

F<40 Hz

” or “

F>70 Hz

” and phase

detection does not start.

3. When a voltage higher than or equal to 100V is detected, the

instrument gives an acoustic signal (buzzer) and the
message “

Meas

” is shown on the display. Do not press any

key and keep the test lead connected to L1 phase cable.

Mod Go

P h S e q


P H 1



M e a s

19/01-17:00:00

4. Once phase L1 acquisition is complete, the displays shows

the screen here to the side. Disconnect the test lead from
phase L1 cable.

Mod Go

P h S e q


D i s c o n .



W a i t

19/01-17:00:00

5. The instrument shows the screen here to the side, and waits

for the detection of phase L2.
Connect the test lead to phase L2 cable.

Mod Go

P h S e q


P H 2



W a i t

19/01-17:00:00




WARNING

If more than 3 seconds elapse before detecting phase L2, the instrument
displays the message “

Time Out

”.

It is necessary to repeat the measuring cycle from the beginning, by
pressing key F4 (Go) and starting from step 1 again.




6. When a voltage higher than or equal to 100V is detected, the

instrument gives an acoustic signal (buzzer) and the
message “

Meas

” is shown on the display. Do not press any

key and keep the test lead connected to L2 phase cable.

Mod Go

P h S e q


PH2



M e a s

19/01-17:00:00