Caution – HT instruments SOLAR300N User Manual

Page 159

Advertising
background image

SOLAR300 - SOLAR300N

EN - 157

CAUTION

BEFORE CONNECTING THE DC CLAMPS TO THE CONDUCTORS

Switch on the clamp, check the LED indicating the status of the clamp’s
internal batteries (if present), select the correct range, press the ZERO key
on the DC clamp and check on the display of SOLAR300N the actual
zeroing of the corresponding Idc value (values up to 0.02A are acceptable).

10. Fig. 247Insert the DC current clamp onto the positive output conductor of the string,

respecting the direction of the arrow found on the clamp itself as indicated in Fig.
246 or Fig. 247. Position the clamp toroid as far as possible from the inverter and from the
negative output conductor of the string itself.

11. Repeat the operations described in the two steps above for other possible DC power

trackers to be monitored by using the IDC2 and IDC3 inputs according to the number of DC
inputs set (see § 5.3.2.5).

12. Connect the VAC1 and N inputs of unit MPP300 to the Phase and Neutral conductors

respectively, respecting the polarities and the colours indicated in Fig. 246 or Fig. 247.
In case of three-phase systems in which no Neutral conductor is available, connect input N
to earth.

13. In case of inverter with three-phase output (see settings in § 5.3.1), repeat the operation

described in the step above for the remaining phases by using the VAC2 and VAC3 inputs
of MPP300.

14. Fig. 247Connect the AC clamp to the Phase L1 conductor, respecting the direction

of the arrow found on the clamp itself as indicated in Fig. 246. and/or Fig. 247. Position
the clamp toroid as far as possible from the inverter and from the Neutral conductor.
Connect the clamp output to the IAC1 input of MPP300.

15. In case of inverter with three-phase output (see settings in § 5.3.1), repeat the operation

described in the step above for the remaining phases by using the IAC2 and IAC3 inputs of
MPP300.

16. Restore the operation of the electrical system being measured.

17. The display of SOLAR300N will show the values of

the general electrical parameters of the system
being measured.

In particular, in this screen:
Pdc = General dc power (sum of the string powers)
Pac = ac power (if single-phase) or sum of the ac
powers (if three-phase)

We recommend checking that the values of the
electrical parameters (Pnom, Pdc, Pac) and of the ac
performance (

ac) are consistent with the system

being measured (e.g.:

ac > 1 is not physically

acceptable).




RUN

Advertising
This manual is related to the following products: