HT instruments VEGA78 User Manual

Page 115

Advertising
background image

VEGA78

EN - 113

9.2. GENERAL

FEATURES

Real time values

General network parameters:

Voltages, Currents, Powers, Cos

Unbalance, THD%, Harmonics, Energies

Signals waveforms:

Voltages, Currents, harmonics histograms

Vectorial diagrams:

Voltages, Currents

Recordings

Parameters:

Each general parameters + energies

Number of selectable parameter:

Max 251

Integration period:

1, 2, 5, 10, 30sec, 1, 2, 5, 10, 15, 30, 60min

Recording time:

>3 months with 251 parameters@15min

Display

Characteristics:

Graphic TFT with backlight, ¼ “ VGA (320x240pxls)

Touch screen:

Yes

Number of colours:

65536

Brightness adjustment:

Programmable

Operative system and memory

Operative system:

Windows CE

Internal memory:

About 15Mbytes (about 32Mbytes with Compact Flash)

PC interface:

USB

Power supply

Internal power supply:

Li-ION, 3.7V rechargeable battery, autonomy >6 hours

External power supply:

AC/DC adapter

Auto power OFF:

After 5min of no use (without external adapter)

Mechanical characteristics

Dimensions:

235(L) x 165(W) x 75(H) ; 9(L) x 6(W) x 3(H) inch

Weight (included battery):

1.0kg (35 ounces)

Reference standards

Safety of meter:

IEC/EN61010-1

Technical literature:

IEC/EN61187

Safety standard accessories:

IEC/EN61010-031, IEC/EN61010-2-032

Insulation: Double

insulation

Pollution degree:

2

Max altitude:

2000m (6562 ft) (*)

CAUTION

(*) Information about the use of meter at altitude from 2000 to 5000m

As for voltage inputs B1, B2, B3, B4, BE the instrument is to be considered downgraded to
overvoltage category CAT III 600V to ground, max 1000V between inputs or CAT IV 300V
to ground, max 600V between inputs. Markings and symbols indicated on the instrument
are to be considered valid when using it at altitude lower than 2000m

Overvoltage category (@ 2000m):

CAT IV 600V to Ground, max 1000V between inputs

Harmonics:

IEC/EN61000-4-30 Class B, EN50160

Unbalance:

IEC / EN61000-4-30 Class B, EN50160

9.3. ENVIRONMENT
9.3.1. Climatic

condition

Reference calibration temperature:

23 ± 5°C; (73 ± 41°F)

Working temperature:

0 ÷ 40°C; (32 ÷ 104°F)

Relative humidity:

<80%HR

Storage temperature:

-10 ÷ 60°C; (14 ÷ 140°F)

Storage relative humidity to:

<80%HR

This instrument complies with the prescriptions of the European directive on low voltage

2006/95/CE (LVD) and EMC 2004/108/CE

9.4. ACCESSORIES

See enclosed packing list.

Advertising