In the example of Fig. 102 the typical customized configuration called “GENERIC PLANT”
was defined and can be loaded by pressing the SAVE or ENTER keys (or the smart icon

). This configuration cab be removed in any time by pressing F2 key (or the REM at display).

The warning message “Delete selected configuration?” is shown by meter. Press “Ok” to
complete the operation. Please note that the 5 predefined configuration and the DEFAULT
configuration cannot be removable by user.

Press ESC (or the smart icon ) to quit without saving any modify. Below the selected
parameters for each of predefined configuration are shown:




VOLTAGE ANOMALIES

MENU GENERAL

PARAMETER

SETTINGS

SYSTEM

Analyzer Settings

System

Not modified

Each system

Freq[Hz]

Clamp Type

FS Clamp[A]

VT Ratio

Analyzer Settings - Advanced

Zoom Graphics

Harm. Type

Harm. Values

Zoom 1st Harm.

Average Values

Recording Settings

Comments VOLTAGE

ANOMALIES

Each system

Start Not

modified

Stop Not

modified

Integration period

1min

Cogeneration OFF

General Parameters

V1N, VN-PE, Hz

Single phase

V12, V23, V31, Hz

3-wire, ARON

V1N, V2N, V3N, VN-PE,

Average (if activated), Hz

4-wire

Voltage harmonics

OFF

Each system

Current harmonics

OFF

Voltage anomalies

ON

Ref. Voltage anomalies

230V Single,

4-wire

400V 3-wire,

ARON

Up threshold anomalies

+6%

Each system

Low threshold anomalies

-10%

Unbalance

Not available

Single phase

ON 3/4-wire,

ARON

Table 7: Selected parameters of VOLTAGE ANOMALIES configuration