Caution, Vega78, En - 59 – HT instruments VEGA78 User Manual

Page 61: Warning, Missed external adapter, Wrong phase sequence, Negative active powers, Wrong vref voltage anomalies, Too many selected parameters

Advertising
background image

VEGA78

EN - 59

CAUTION

For recordings ALWAYS use the external power supply even though the
instrument allows the operator to perform a recording using internal
batteries.


After starting a recording a preliminary real time evaluation about the situation on electrical
installation it’s important in order to perform a correct settings, using the predefined
configurations (see § 5.4.9) if necessary.
The below warning message can be shown by meter after pressing of GO/STOP key:

Warning

Too many selected parameters

Fig. 106: Warning message of too many selected parameters

In this case of too many parameters were selected it is necessary to disable them inside
“Recordings Settings” section in order to start a correct recording.
After pressing GO/STOP key a possible warning message window is shown by meter.
Inside this window message the internal item can be different as for type and number. This
warning message, which does not block the recording start, is important for user to correct
possible errors performed during meter’s setting:

Warning

Missed external adapter

Wrong phase sequence

Negative active powers

Wrong Vref voltage anomalies

Ok

Cancel

Fig. 107: Warning message errors screen

Below the meaning of the above s of warning windows screen:

Type of error

Description

Missed external adapter

Connect the external adapter to meter before start
recording

Wrong phase sequence

The value of “SEQ” parameter in Real Time Values
section (see § 5.2.1) is different from the correct
123”. Check the phase sequence value of V1, V2, V3
voltages

Negative active powers

One or more values of P1, P2, P3 Active Powers is
negative (see § 5.2.1). Reversing if necessary the
transducer clamps of 180 degrees on phase cables in
order to obtain always positive values (except
cogeneration cases)

Wrong Vref voltage anomalies

The nominal reference voltage value for voltage
anomalies is not compliance to the type of selected
system (see § 5.4.7)

Table 11: Description of errors before start a recording