INOR IPAQ-22LX User Manual

Page 2

Advertising
background image

LIMITED WARRANTY

INOR Process AB, or any other affiliated company within the Inor Group (hereinafter jointly referred to as

”Inor”), hereby warrants that the Product will be free from defects in materials or workmanship for a period

of five (5) years from the date of delivery (”Limited Warranty”). This Limited Warranty is limited to repair

or replacement at Inor’s option and is effective only for the first end-user of the Product. Upon receipt of

a warranty claim, Inor shall respond within a reasonable time period as to its decision concerning:

1 Whether Inor acknowledges its responsibility for any asserted defect in

materials or workmanship; and, if so,

2 the appropriate cause of action to be taken (i.e. whether a defective

product should be replaced or repaired by Inor).

This Limited Warranty applies only if the Product:

1 is installed according to the instructions furnished by Inor;

2 is connected to a proper power supply;

3 is not misused or abused; and

4 there is no evidence of tampering, mishandling, neglect, accidental damage, modification

or repair without the approval of Inor or damage done to the Product by anyone other

than Inor.

This Limited Warranty is provided by Inor and contains the only express warranty provided.

INOR SPECIFICALLY DISCLAIMS ANY EXPRESS WARRANTY NOT PROVIDED HEREIN AND

ANY IMPLIED WARRANTY, GUARANTEE OR REPRESENTATION AS TO SUITABILITY FOR

ANY PARTICULAR PURPOSE, PERFORMANCE, QUALITY AND ABSENCE OF ANY HIDDEN

DEFECTS, AND ANY REMEDY FOR BREACH OF CONTRACT, WHICH BUT FOR THIS PRO-

VISION, MIGHT ARISE BY IMPLICATION, OPERATION OF LAW, CUSTOM OF TRADE OR

COURSE OF DEALING, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND

FITNESS FOR A PARTICULAR PURPOSE. EXCEPT AS PROVIDED HEREIN, INOR FURTHER

DISCLAIMS ANY RESPONSIBILITY FOR LOSSES, EXPENSES, INCONVENIENCES, SPECIAL,

DIRECT, SECONDARY OR CONSEQUENTIAL DAMAGES ARISING FROM OWNERSHIP OR

USE OF THE PRODUCT.
Products that are covered by the Limited Warranty will either be repaired or replaced at the option of

Inor. Customer pays freight to Inor, and Inor will pay the return freight by post or other “normal” way of

transport. If any other type of return freight is requested, customer pays the whole return cost.

DATA (shortform)

ORDERING TABLE

IPAQ-21LX/-22LX EX-DATA

Approval Demko 03 ATEX 134845X

II (1) G [Ex ia] IIC

II (1) D [Ex iaD]

Input (terminals 11-14, 21-24)

(Intrinsically safe sensor terminals)

U

o

: 15 V

I

o

: 13 mA

L

o

: 100 mH

C

o

: 550 nF

The IPAQ-21LX/-22LX shall be placed outside the hazardous area.

The IPAQ-21LX/-22LX contains no serviceable parts.

In case of repair, the product must be sent to INOR or your dealer.

IPAQ-21LX/-22LX must be installed in safe area.

IPAQ-21LX/-22LX/-21L/-22L are designed to fit on a standard

DIN Rail.

INSTALLATION

Fig 1.

1. Power supply, load and output

signal are connected according

to figure below.

2. Input signal is connected

according to one of the figures 2-8

CABLE LENGTH

For Ex-version IPAQ-21LX/22LX observe that maximum input cable length

is restricted by cable parameters. The total capacitance, inductance and

ratio inductance/resistance must be within the limits given by the certificate

for the transmitter and EN 500020, EN60079-14.

If the connected sensor includes capacitance and inductance these values

must be subtracted from Co and Lo

To calculate maximum length of the cable, use the data-sheet for the

cable to get the cable capacitance/meter. To get the maximum length of

the cable use the formula:

Lengthmax= Co/C where Lmax is in meter, Co is from Ex-data above

and C is cable capacitance/m (nF/m)

Lengthmax= Lo/L where Lmax is in meter, Lo is from Ex-data above

and L is cable inductance/m (mH/m)

Use the smallest Lengthmax of these two calculated values.

Input

Output

Fig 2

Fig 3

Fig 4

Fig 5

Fig 6

Fig 7

Fig 8

RTD

4-wire connection

RTD

3-wire connection

Pt100

Diff temperature T1 > T2

Potentiometer

3-wire connection

Potentiometer

4-wire connection

Voltage

mV

Thermocouple

IPAQ-21L,

Non-Ex, 1-Ch

70IP21L001

IPAQ-22L,

Non-Ex, 2-Ch

70IP22L001

IPAQ-21LX,

Ex, 1-Ch Fixed conn.

70IP21LX01

IPAQ-21LX,

Ex, 1-Ch Plug-in conn. 70IP21LX02

IPAQ-22LX,

Ex, 2-Ch Fixed conn.

70IP22LX01

IPAQ-22LX,

Ex, 2-Ch Plug-in conn. 70IP22LX02

PC Configuration Kit

70CFG00092

Configuration

70CAL00001

!

Cover with the delivered plastic plugs

during operation.

IPAQ-21L/-22L have screw plug connectors with coding for connecting

to the right position.

IPAQ-21LX/-22LX can be supplied with either fixed terminals or screw

plug-in connectors with coding.

Power supply:

8 to 36 VDC

Isolation in/out:

1500 VAC

Output:

4-20 mA limit 23 mA

Operating temperature: IPAQ-21LX/-22LX -20

Tamb

+60 °C

IPAQ-21LX/-22LX -4

Tamb

+140 °F

IPAQ-21L/-22L

-20

Tamb

+70 °C

IPAQ-21L/-22L

-4

Tamb

+158 °F

R

LOAD

(Ω)

Supply voltage U (VDC)
R

LOAD

=(U-8)/0.022

Ri ≤ 10 Ω