INOR IPAQ-LX GB User Manual

Page 2

Advertising
background image

CONNECTIONS

Item

Part No.

IPAQ-L

70IPL00001

IPAQ-LX (ATEX)

70IPLX0001

IPAQ-LX (FM, CSA)

70IPLX1001

IPAQ-L(mA) Current input only

70IPL00003

Software and cable

Configuration kit IPRO with cables

70CFG00092

LIMITED WARRANTY

INOR Process AB, or any other affiliated company within the Inor Group (her-

einafter jointly referred to as ”Inor”), hereby warrants that the Product will be

free from defects in materials or workmanship for a period of five (5) years from

the date of delivery (”Limited Warranty”). This Limited Warranty is limited to

repair or replacement at Inor’s option and is effective only for the first end-user

of the Product. Upon receipt of a warranty claim, Inor shall respond within a

reasonable time period as to its decision concerning:

1 Whether Inor acknowledges its responsibility for any asserted defect in

materials or workmanship; and, if so,

2 the appropriate cause of action to be taken (i.e. whether a

defective product should be replaced or repaired by Inor).

This Limited Warranty applies only if the Product:

1 is installed according to the instructions furnished by Inor;

2 is connected to a proper power supply;

3 is not misused or abused; and

4 there is no evidence of tampering, mishandling, neglect, accidenta da-

mage, modification or repair without the approval of Inor or damage

done to the Product by anyone other than Inor.

This Limited Warranty is provided by Inor and contains the only express war-

ranty provided.

INOR SPECIFICALLY DISCLAIMS ANY EXPRESS WARRANTY NOT

PROVIDED HEREIN AND ANY IMPLIED WARRANTY, GUARANTEE

OR REPRESENTATION AS TO SUITABILITY FOR ANY PARTICULAR

PURPOSE, PERFORMANCE, QUALITY AND ABSENCE OF ANY HIDDEN

DEFECTS, AND ANY REMEDY FOR BREACH OF CONTRACT, WHICH BUT

FOR THIS PROVISION, MIGHT ARISE BY IMPLICATION, OPERATION

OF LAW, CUSTOM OF TRADE OR COURSE OF DEALING, INCLUDING

IMPLIED WARRANTIES OF MER-CHANTABILITY AND FITNESS

FOR A PARTICULAR PURPOSE. EXCEPT AS PROVIDED HEREIN,

INOR FURTHER DISCLAIMS ANY RESPONSIBILITY FOR LOSSES,

EXPENSES, INCONVENIENCES, SPECIAL, DIRECT, SECONDARY OR

CONSEQUENTIAL DAMAGES ARISING FROM OWNERSHIP OR USE

OF THE PRODUCT.
Products that are covered by the Limited Warranty will either be repaired or

replaced at the option of Inor. Customer pays freight to Inor, and Inor will pay

the return freight by post or other “normal” way of transport. If any other type

of return freight is requested, customer pays the whole return cost.

DATA (shortform)

ORDERING TABLE

IPAQ-LX EX-DATA

Approval Demko 03 ATEX 134461X

CE 0539

II (1)G [Ex ia] IIC

Control Drawing 88DRW00022

IPAQ-L/LX/L(mA) are designed to fit on a standard DIN Rail.

IPAQ-LX must be installed in safe area.

Connect input, output and power supply acc. to fig. 1-10.

INSTALLATION

Power supply: IPAQ-L, IPAQ-L(mA)

7.5 to 36 VDC

IPAQ-LX

8 to 30 VDC

Isolation in/out:

1500 VAC

Output:

4-20 mA

Operating temperature:

-20 to +70 °C

T

1

T

2

6

+ -

5

mV

RTD

(Pt100)

T/C

RTD

100%

0%

RTD

RTD

(Pt100)

100%

0%

RTD

4-wire connection

Pt100

Diff temperature T

1

> T

2

Potentiometer

3-wire connection

Potentiometer

4-wire connection

Voltage

mV

Thermocouple

Supply voltage U (VDC)

RTD

3-wire connection

Fig 3

Fig 4

Fig 5

Fig 6

Fig 7

Fig 8

Fig 9

IPAQ-L, IPAQ-L(mA)

IPAQ-LX

!

!

Fig 1

Fig 2

IP

A

Q-L(mA

)

R

LOAD

=(U-7.5)/0.22 IPAQ-L, IPAQ-L(mA)

R

LOAD

=(U-8)/0.22 IPAQ-LX

Fig 10

Current

mA

Approval FM, J.I. 0D6A8.AX, CSA 2007 Certificate 1863602

Class I, II and III, Division 1, Group A, B, C, D, E, F and G

Control Drawing 3-7852

Output (terminals 5-6)

(current loop)

U

i

:

30 VDC

I

i

:

100 mA

P

i

:

0,9 W

L

i

:

0 mH

C

i

:

1 nF

Input (terminal 1-2-3-4)

(Intrinsically safe sensor terminals)

U

o

:

30 V

I

o

:

27 mA

L

o

:

50 mH

C

o

:

52 nF

The equipment must be electrically connected (terminal 5 and 6)

via a certified isolating interface/zener barrier -and shall be

placed outside the hazardous area.

1)

Ri ≤ 10 Ω

1)