DATA (shortform)

CONNECTIONS

ORDERING TABLE

MESO-HX Ex-DATA

Approval Demko 03 ATEX 134077X

II 1G Ex ia IIC T4/T5/T6

Control Drawing 88DRW00053

Approval FM, J.I. 6D9A4.AX, CSA 2007 Certificate 1863602

Class I, II and III, Division 1, Group A, B, C, D and G

Control Drawing 3-7967

Output (current loop)

U

i

:

30 VDC

I

i

:

100 mA

P

i

:

900 mW

L

i

:

1 mH

C

i

:

1 nF

MESO-HX must be powered from an certified isolating power supply or

zener barrier, placed outside the hazardous area. MESO-HX shall be
mounted in an Ex-compatible housing having protection IP20 or better.

INPUTS

Fig 9.

Power supply

1)

: Meso-H 10 - 42 VDC

2)

Meso-L

11 - 42 VDC

2)

Meso-HX 12 - 30 VDC/max 100 mA/0.9W

1)

When communicating acc to HART the load must be more than 250 ohm.

2)

Supply voltage over 36V demands at least 250 ohm´s load

Load

Load

Load

Meso-H

Meso-L

1. Power supply, load and output signal are connected according

to figure above

2. Input signal is connected according to one of the figures 1-9

CABLE LENGTH

To calculate maximum

length of the cable for

reliable communication,

add load resistance and

approximated cable re-

sistance. Please note that

the loop resistance for

reliable communication

must be in the range 230

– 1100 Ohm, 250 Ohm is

a commonly used value.

In the data-sheet for the cable you get the cable capacitance/meter. Use the

R value you calculated and the cable capacitance/meter together with the

diagram above to get the maximum length of the cable. For multidrop mode,

use the formula below.

The cable length can also be calculated according to the formula:

L = 65*10

6

/ (R * C) – (Cn*5000 +10 000) / C

Where:

L: is the cable length (m)

R: is load resistance (including resistance of barrier)+cable resistance (ohm)

C: is cable capacitance/m (pF/m)

Cn: is the number of Meso transmitters in the loop.

L can also be changed to ft, if so C is given in pF/ft.

For Ex-version MESO-HX also the restrictions on cable capacitance Ci

and inductance Li stated in the Certificates and Approval documents

must be observed. Also national and regional standards and regulations

must be consulted.

l

l

l

Meso-HX

Fig12

Fig10

Fig11

see ”Cable Length”

12-30 VDC

MESO-HX may only be

connected to transducers

complying with ”Simple

Apparatus” acc. to

EN 60079-11:2007 § 5.7

1)

1)

R

i

≤ 10

Ambient temperature:

T4: -40

o

C ≤ Tamb ≤ +85

o

C

T5: -40

o

C ≤ Tamb ≤ +65

o

C

T6: -40

o

C ≤ Tamb ≤ +50

o

C

Service temperature ≤ max ambient temperature

MESO-HX must be installed in an enclosure having

an Ingress Protection suitable for the actual use

but at least IP20.

If MESO-HX is mounted in a housing (head) made of light metals and

installed in hazardous area make sure the content of magnesium (Mg)

in the light metal is less than 6%.

If MESO-HX is mounted in a housing which is isolated from ground and

can be charged to an ignition capable level, then the housing shall be

electrostatically grounded when installed in hazardous area.

!