8.2.3. Moving inside the Menu System

Pressing ESC will stop displaying measurements, and show the first
menu item, DISPLAY. From here, the four buttons allow the user to
move around the menu tree, as indicated by the arrows. Press the
down arrow repeatedly; the menu display will cycle through each of
the top level (Level 1) menu items. Refer to the menu structure dia-
gram on the following pages as you move around

NOTE: Each menu item has its level (1 - 4) displayed at the beginning
of the top line.

The four buttons also allow the user to move up and down the pick-
lists, as indicated by the arrows. Also, pressing ESC moves one from
the current level to the next higher level. Pressing ESC within the top
level menu returns the user to the MEASURE block.

8. Local Configuration Instructions VFM 3100

8.1. Introduction

Local configuration of the VFM 3100 is accomplished via four multi-
function pushbuttons on the local keypad/display shown below.
A functional overview of the Menu Tree is presented in Table 12.

8.2. Using the Local Configurator

8.2.1. Measurements (MEASURE)

The system starts up displaying the measured Flowrate (FLOW), the
Total (TOTAL), or the Flow and Total (BOTH), in an alternating fashion,
depending on the selection made in the Calibrate/Show menu.

8.2.2. Display Bar Indicator

The analog bar indicator at the top of the display indicates the flow
measurement, as a percentage of the upper range value.

NOTE: If the flow measurement is out-of-range, the bar indicator will
blink. If the transmitter is off-line, the middle four bars of the bar indi-
cator will blink.

In TEST/SET DIG, the bar indicator continues to display the flow
measurement. However, in TEST/SET MA, it displays the per-
centage of span set.

49

Level 1

Level 2

Function

MEASURE

Display Flowrate and Total

DISPLAY

OPTIONS

Display Transmitter and Output Options

PARAMS

Display Fluid and Application Parameters

TAGS

Display Flowtube and ID Parameters

CALIB

SHOW

Set Measurement Display Mode

LFCI

Set Low Flow Cut-In

RESET TOTAL

Set Total to Zero

CAL 4 mA

mA Calibration @ 4 mA

CAL 20 mA

mA calibration @ 20 mA

TEST

DIAG

Display Status

SET DIG

Set Digital Output for Loop Calibration

SET MA

Set 4-20 mA Output for Loop Calibration

SET HZ

Set Scaled Pulse Output for Loop Calibration

SELFTST

Activate Transmitter Self-Test

XMTTEMP

Display Transmitter Temperature

CONFIG

OPTIONS

Select Transmitter Options

OUTPUT

Select Output Option

FLUID

Enter Fluid Parameters

UNITS

Enter Units, URV, and Damping

BIAS

Enter Application Parameter

TAGS

Enter Identification Parameters

NEWTUBE

Enter Flowtube Parameters

PASSWD

Change Passwords

Table 12. Menu Tree Functional Overview