Diagnosis to control system in case of

Manufacturer specific Ident. Number (4531hex)

Profile specific Ident. Number (9740hex)

Profile specific Ident. Number (9700hex)

Bit Number

sup

p

orted

De

sc

ription

Remedy

16

yes

Error appears

-

17

yes

Error disappears

-

24

1

Hardware failure electronics

Restart the device. If the error occurs again: send the device back

to the manufacturer with an indication of the error.

27

1

Electronic temperature too high

Electronic temperature below -40°C or above +85°C. Comply with

the application limits with regard to temperature of the medium

and ambient temperature. If the process conditions are within the

specified limits: send the device back to the manufacturer with an

indication of the error.

28

1

Memory error

Reset the device to Factory/Default settings. If the error occurs

again: send the device back to the manufacturer with an

indication of the error.

29

1

Measurement failure

Check process conditions (Flow/Level, Temperature). If the

process conditions are within the specified limits: send the device

back to the manufacturer with an indication of the error.

34

1

Configuration invalid

Reset the device to Factory/Default settings. If the error occurs

again: send the device back to the manufacturer with an

indication of the error.

35

yes

Restart

Device is restarted because of power-up or warmstart request. In

case of unexpected restart: send the device back to the

manufacturer with an indication of the error.

36

yes

Coldstart

Device is reset to its Factory/Default settings because of a user

request or exchange of the basic module (serial number is

changed). Recover user specific parameter settings.

37

yes

Maintenance required

Linearization or temperature compensation is not operating

correct. See for detailed failure message or send the device back

to the manufacturer with an indication of the error.

39

yes

Ident_Number violation

Ident. Number Selector was modified while cyclic data transfer

was active. To clear this message perform one of the following

actions:

Reset Ident. Number Selector to its former setting

Stop cyclic data transfer

Restart the device

40

2

Maintenance alarm

Check detailed diagnosis. Restart the device. If the error occurs

again: send the device back to the manufacturer with an

indication of the error.

42

2

Function check

Simulation is active. Disable simulation to clear this message.

43

2

Invalid process condition

Check process conditions (Flow/Level, Temperature). If the

process conditions are within the specified limits: send the device

back to the manufacturer with an indication of the error.

55

yes

Extension available

Refer to detailed diagnosis in bits 56 to 103.

56

3

SE – ROM error

Restart the device. If the error occurs again: send the device back

to the manufacturer with an indication of the error.

57

3

SE – FRAM error

Restart the device. If the error occurs again: send the device back

to the manufacturer with an indication of the error.

58

3

SE – Memory corruption detected

Restart the device; if the error occurs again the device must be

sent back to the manufacturer with an indication of the error.