2.3 PROFIBUS PA Profile implementation

The PROFIBUS PA Profile 3.02 defines standardized parameters and functions for PROFIBUS
devices used for process control. It describes a PROFIBUS device as a function block application,
i.e. parameters and functions are grouped into different blocks. In the ESK4-PA transmitter the
following blocks are implemented:

The Analog Input Function Block and the Totalizer Function Blocks provide the data interface
towards a process control system (e.g. a PLC); i.e. their input/output data can be read/written by
the control system. In a PROFIBUS network this is done via cyclic communication services.

From the PROFIBUS point of view the ESK4-PA transmitter is designed as a modular device with
three slots. While the Analog Input Function Block is assigned (as virtual module) to slot 1 the
Totalizer Function Blocks are assigned (as virtual modules) to slot 2 and 3. This assignment is
fixed and cannot be modified by the user. Nevertheless the measuring data for each Function
Block is selectable according to the following tables:

Device calibrated for Volume Flow

The calibration units are used as default units.

Block

Usage

1 Physical Block (PB)

contains identification and diagnosis parameters of the device

1 Flow Transducer Block

(TB-Flow)

contains parameters and functions to control the flow measurement

1 Level Transducer Block

(TB-Level)

contains parameters and functions to control the level measurement

1 Analog Input Function Block

(AI-FB)

contains parameters and functions to control the measuring output;

provides the measuring value(s)

2 Totalizer Function Blocks

(Tot-FB)

contains parameters and functions to control/provide the counter

value(s)

Slot

Slot

Slot

Slot

Module type

Module type

Module type

Module type

Measuring data

Measuring data

Measuring data

Measuring data

1

1

AI-FB

Volume flowrate (Default setting)

Mass flowrate

Board temperature

2

Totalizer-FB

Totalized volume flowrate (Default setting)

Totalized mass flowrate

3

Totalizer-FB

Totalized volume flowrate

Totalized mass flowrate (Default setting)

1 Selection of measuring data can be changed by modifying the channel parameter via acyclic PROFIBUS services.