Commissioning / operation – KROHNE H250 M40 PROFIBUS PA User Manual
Page 25

COMMISSIONING / OPERATION
4
25
H250 M40 ESK4
www.krohne.com
03/2014 - 4002251801 - AD H250/M40 PROFIBUS R01 en
59
3
SE – Crystal failure
The device must be sent back to the manufacturer with an
indication of the error.
60
3
SE – Invalid reference voltage
61
3
SE – Sensor A failure
62
3
SE – Sensor B failure
63
3
SE – Temperature sensor failure
64
3
SE – Communication failed
65
3
SE – Temperature out of range
Electronic temperature below -40°C or above +85°C. Comply with
the application limits with regard to temperature of the medium
and ambient temperature. If the process conditions are within the
specified limits: send the device back to the manufacturer with an
indication of the error.
66
3
SE – PV out of upper limit
PV larger than 150% of the calibrated range. Reduce flow/level. If
the process conditions are within the specified limits: send the
device back to the manufacturer with an indication of the error.
67
3
SE – No pre-linearization
Activate linearization or carry it out again (HART® communication
and linearization software are required; the original calibration
values must be known), or send the device back to the
manufacturer for linearization.
68
3
SE – No temperature compensation
The device, together with an indication of the error, must be sent
back to the manufacturer for checking.
69
3
SE – No output linearization
Activate linearization or carry it out again (HART® communication
and linearization software are required; the original calibration
values must be known), or send the device back to the
manufacturer for linearization.
70
3
SE – Temperature out of limits
Electronic temperature below -45°C or above +125°C. Comply
with the application limits with regard to temperature of the
medium and ambient temperature. If process conditions are
within the specified limits: send the device back to the
manufacturer with an indication of the error.
72
3
SE not connected
Check connection between basic module and PROFIBUS module.
If the error remains: send the device back to the manufacturer
with an indication of the error.
76
3
SE parameter update error
Incompatible combination between basic module and PROFIBUS
module: send the device back to the manufacturer with an
indication of the error.
77
3
SE not supported
78
3
SE power supply failure
Restart the device. If the error occurs again: send the device back
to the manufacturer with an indication of the error.
79
3
SE – PV out of range
PV larger than 110% of the calibrated range. Reduce flow/level.
94
3
PA – Runtime data failure
Reset the device to Factory/Default settings. If the error occurs
again: send the device back to the manufacturer with an
indication of the error.
95
3
PA – Runtime execution failure
96
3
PA – CPU board failure
Restart the device. If the error occurs again: send the device back
to the manufacturer with an indication of the error.
97
3
PA – CPU ROM failure
98
3
PA – CPU RAM failure
99
3
PA – Ext. RAM failure
101
3
PA – SPC4-2 failure
102
3
PA – FRAM device failure
103
3
PA – FRAM data failure
Reset the device to Factory/Default settings. If the error occurs
again: send the device back to the manufacturer with an
indication of the error.
1 Indication is supported if Classic Diagnosis is active only.
2 Indication is supported if Condensed Diagnosis is active only.
3 Indication is supported in cyclic diagnosis only if Ident. Number 4531hex is active. Nevertheless it is available always via acyclic access
(e.g. by using DD/DTM).
AD_H250_M40_PB_PA_R01_en_4002251801_PRT.book Page 25 Friday, March 21, 2014 1:14 PM