Diagnosis to control system in case of

Compatibility mode (ESK3-PA: F201hex),

Compatibility mode (Profile: 9740hex):

Bit

Nu

mbe

r

supported

Description

Remedy

16

yes

Error appears

-

17

yes

Error disappears

-

24

yes

Hardware failure electronics

Restart the device.

Reset the device to Factory/Default settings.

Check connection between basic module and

PROFIBUS module.

If the error occurs again: send the device back to

the manufacturer with an indication of the error.

28

yes

Memory error

Reset the device to Factory/Default settings. If the

error occurs again: send the device back to the

manufacturer with an indication of the error.

29

yes

Measurement failure

Refer to detailed diagnosis in bits 56 to 73. If no

further information is available: send the device

back to the manufacturer with an indication of the

error.

35

yes

Restart

Device is restarted because of power-up or

warmstart request. In case of unexpected restart:

send the device back to the manufacturer with an

indication of the error.

36

yes

Coldstart

Device is reset to its Factory/Default settings

because of a user request or exchange of the basic

module (serial number is changed). Recover user

specific parameter settings.

39

yes

Ident_Number violation

Ident. Number Selector was modified while cyclic

data transfer was active. To clear this message

perform one of the following actions

Reset Ident. Number Selector to its former
setting

Stop cyclic data transfer

Restart the device

55

yes

Extension available

Refer to detailed diagnosis in bits 56 to 73

56

1

IRAM Error

Restart the device. If the error occurs again: send

the device back to the manufacturer with an

indication of the error.

57

1

XRAM error

58

1

ROM error

59

1

SPC4 Error

60

1

ADC Error

Check environment conditions. If they are within

the specified limits: send the device back to the

manufacturer with an indication of the error.

61

1

EEPROM Error

Restart the device. If the error occurs again: send

the device back to the manufacturer with an

indication of the error.

62

1

FRAM Error

Reset the device to Factory/Default settings. If the

error occurs again: send the device back to the

manufacturer with an indication of the error.

64

1

No ADC ZeroCal

Activate linearization or carry it out again (HART®

communication and linearization software are

required; the original calibration values must be

known), or send the device back to the

manufacturer for linearization.

65

1

No ADC FullCal

AD_H250_M40_PB_PA_R01_en_4002251801_PRT.book Page 26 Friday, March 21, 2014 1:14 PM