Installation and operating instructions

31

BATCHFLUX



→ VALUE P = Set pulse value per unit volume,
(appears only when “PULSE/VOL.“ has been set under “SELECT P“) press key

→

• XXXX PulS/m

3

• XXXX PulS/Liter
• XXXX PulS/US.Gal
• XXXX PulS/ user-defined unit,

factory-set is “Liter“, see Sect. 5.12.


Select with keys

↑ and ↓.

Transfer to number setting with key

→, 1st digit (cursor) flashes.


Set numerical value
• XXXX (Setting range depends on

pulse width and full-scale range:

P

min

= F

min

/ Q

100%

P

max

= F

max

/ Q

100%

)


Change flashing digit (cursor) with keys

↑ and ↓ ,

Shift cursor 1 place to right or left with keys

→ und ← .

Press key

↵ to return to Fct. 1.6 PULS.OUTP. P.

or

→ VALUE P = Set pulse value per unit time,
(appears only when “PULSE/TIME“ has been set under “SELECT P“), press key

→

• XXXXX PulSe/Sec

(max. 10 kHz)

• XXXX PulSe/min
• XXXX PulSe/hr
• XXXX PulSe/ user-defined unit,

factory-set is “hr“, see Sect. 5.12.


Select with keys

↑ and ↓.

Transfer to number setting with key

→, 1st digit (cursor) flashes.


Set numerical value
• XXXX

(Setting range depends on

pulse width)


Change flashing digit (cursor) with keys

↑ and ↓ ,

Shift cursor 1 place to right or left with keys

→ and ←.

Press key

↵ to return to Fct. 1.6 PULS.OUTP. P.


Please refer to Sect. 3.2
“Factory settings“

Refer to Sect. 2.3 for connection diagrams,
and to Sect. 5.14 for characteristics.