KROHNE IFC 020 Converter EN User Manual

Page 35

Advertising
background image

Installation and operating instructions IFC 020

5/4

Current output I 5.6

Fct. 1.05 CURRENT I

Press

→

key.

→

FUNCT. I = Select function for current output, press

→

key

• OFF

(switched off, no function)

• 1 DIR.

(1 flow direction)

• 2 DIR.

(2 flow directions, F/R mode, forward/reverse)

Select using

↑

or

↓

key.

Transfer to subfunction “RANGE I” with

↵

key.

Exceptions: When “OFF” selected, return to Fct. 1.05 CURRENT I.

→

RANGE I = select measuring range, press

→

key

• 0 - 20 mA

fixed ranges

• 4 - 20 mA

• mA (user-defined value) I

0%

– I

100%

(value I

0%

< I

100%

!) 0-16 mA 4-20 mA

Press

→

key to transfer to number setting.

Select with

↑

or

↓

key.

Press key

↵

to transfer to subfunction “I ERROR”.

→

I ERROR = set error value, press

→

key

• 22 mA

(fixed value)

•

0.0 - I

0%

mA (variable value; only variable when I

0%

≥

1 mA, see ”RANGE I“ above)

Select using

↑

or

↓

key.. Press

→

key to transfer to number setting.

Press key

↵

to return to Fct. 1.05 CURRENT I.

Please refer to Sect. 3.2 “Factory settings”.

Refer to Sect. 2.3 for connection diagrams, and to Sect. 5.14 for characteristics.

}