4

OPERATION

26

OPTIWAVE 5200 C

www.krohne.com

09/2013 - 4002500101 - AD FF OPTIWAVE 5200 R01 en

ALARM_STATE

Alarm State

R

A discrete enumeration which gives an indication of whether

the alert is active and whether it has been reported.

Uninitialized

Setting:

Uninitialized / Clear - reported / Clear - not reported / Active -

reported / Active - not reported

TIME_STAMP

Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received – even if another change of

state occurs.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

SUB_CODE

Subcode

R

An enumeration specifying the cause of the alert to be

reported.

VALUE

Value

R

The value of the associated parameter at the time the alert

was detected.

FD_MAINT_MAP

FD_MAINT_MAP

FD_MAINT_MAP

FD_MAINT_MAP

Maintenance Map

Maintenance Map

Maintenance Map

Maintenance Map

RW

This parameter enables or disables conditions to be detected

as active for this alarm category.

Nothing mapped

Setting:

•

(00) Check Function

•

(01) Cond01

•

(02) Cond02

•

(03) Cond03

•

(04) Cond04

•

(05) Cond05

•

(06) Cond06

•

(07) Bad Measurement quality

•

(08) Signal Strong

•

(09) Signal Weak

•

(10) Empty Spectrum invalid

•

(11) Sensor No Signal

•

(12) Sensor Microwave Error

•

(13) Temperature Above +75°C

•

(14) Temperature Below -35°C

•

(15) Overfill Warning

•

(16) Level Lost warning

•

(17) Temperature out of range (warning)

•

(18) Local operation

•

(19) Overfill Error

•

(20) Level lost error

•

(21) Temperature out of range Error

•

(22) Converter Voltage Error

•

(23) Converter ROM Error

•

(24) Converter RAM Error

•

(25) Converter EEPROM Error

•

(26) Sensor not compatible

•

(27) Internal Communication Error

•

(28) Sensor Voltage Error

•

(29) Sensor ROM Error

•

(30) Sensor RAM Error

•

(31) Sensor EEPROM Error