Operation – KROHNE OPTIWAVE 5200 FOUNDATION FIELDBUS User Manual

Page 62

Advertising
background image

4

OPERATION

62

OPTIWAVE 5200 C

www.krohne.com

09/2013 - 4002500101 - AD FF OPTIWAVE 5200 R01 en

Subcode

R

An enumeration specifying the cause of the alert to be

reported.

Other

Setting:

Other: Non-specific error active

BlockConfiguration: Error detected in block configuration

LinkConfiguration: Error detected in link configuration

SimulationActive: Simulation enabled in this block

LocalOverride: Output tracking or faultstate active

DeviceFaultState: DeviceFaultState

DeviceMaintenance: Device needs maintenance soon

InputFailure: Process variable has bad status

OutputFailure: Failure detected in output hardware

MemoryFailure: Memory error detected

LostStaticData: Static parameters cannot be recovered

LostNVData: Non-Volatile parameters cannot be recovered

ReadbackCheck: Failure detected in READBACK

MaintenanceNeeded: Device NEEDS maintenance NOW

PowerUp: Recovery from power failure

OutOfService: Block actual mode is Out of Service

Value

R

The value of the associated parameter at the time the alert

was detected.

0

Setting:

0...255

BYPASS

BYPASS

BYPASS

BYPASS

Bypass

Bypass

Bypass

Bypass

R/W

The normal control algorithm may be bypassed through this

parameter. When bypass is set, the setpoint value (in percent)

will be directly transferred to the output. To prevent a bump

on transfer to/from bypass, the setpoint will automatically be

initialized to the output value or process variable, respectively,

and the path broken flag will be set for one execution.

Uninitialized

Setting:

ON: normal control algorithm bypassed, output based on
setpoint

OFF: normal control

CAS_IN

CAS_IN

CAS_IN

CAS_IN

Cascade Input

Cascade Input

Cascade Input

Cascade Input

R/W

This parameter is the remote setpoint value, which must

come from another Fieldbus block or a DCS block through a

defined link.

-

Status

R/W

Status of CAS_IN

-

Value

R/W

Value of CAS_IN

-

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value

Advertising